Compare Equipment Go Back

G3412 Gas Generator Set
Cat XLM Switchgear
Cat Customizable Switchgear and Controls
Cat Switchgear

Generator Set Specifications

Continuous Rating 423 ekW @0.8pf - - -
Fuel Type Natural Gas, Biogas, Field Gas, Propane - - -
Maximum Electrical Efficiency 37.30% - - -
Maximum Standby Rating 500 ekW @ 0.8pf - - -
Frequency 50 or 60 Hz - - -
RPM 1500 or 1800 rpm - - -

Engine Specifications

Engine Model G3412 - - -
Displacement 1649 in³ - - -
Aspiration NA - - -
Bore 5.4 in - - -
Stroke 6 in - - -

Generator Set Dimensions

Length 179 in - - -
Width 88 in - - -
Height 86 in - - -
Dry Weight - Genset 9664 lb - - -

Technical Summary

Configuration - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc -
Modes of Operation - Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow -
Application - LV and MV ( 208V - 38 kV LV and MV ( 208V - 38 kV) 50 / 60 Hz -
Technical Summary - - - Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers.

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 Per customer specification -

Utility Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 Per customer specification -

Environmental Parameters

Certifications - IBS, CBC, UBC & OSHPD Certified Per customer specification -
Control Panel Enclosure - NEMA 1 or NEMA 3R, Freestanding Construction Per customer specification -
Operating Temperature - 0 degrees to 50 degrees C Per customer specification -
Storage Temperature - -20 degrees C to +60 degrees C Per customer specification -
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 Per customer specification -
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 Per customer specification -

Enclosure Rating

Configuration - - - IP4X

Operating Temperature

Operating Temperature - - - 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F)

Dimensions

Standard Widths - - - 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A.
Standard Heights - - - Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping
Standard Depths - - - 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers

Application

Application - - - LV 380…480 VAC, 50 Hz, 3-Phase.

Modes of Operation

Modes of Operation - - - Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc.
Add a Similar Product:
  • EMCP 4.4 Master Control Panel Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Temporary Connection Boxes Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add
  • XQ125 Rental Power Add