Compare Equipment Go Back

G3412 Gas Generator Set
Cat XLM Switchgear
Cat Customizable Switchgear and Controls

Generator Set Specifications

Continuous Rating 423 ekW @0.8pf - -
Fuel Type Natural Gas, Biogas, Field Gas, Propane - -
Maximum Electrical Efficiency 37.30% - -
Maximum Standby Rating 500 ekW @ 0.8pf - -
Frequency 50 or 60 Hz - -
RPM 1500 or 1800 rpm - -

Engine Specifications

Engine Model G3412 - -
Displacement 1649 in³ - -
Aspiration NA - -
Bore 5.4 in - -
Stroke 6 in - -

Generator Set Dimensions

Length 179 in - -
Width 88 in - -
Height 86 in - -
Dry Weight - Genset 9664 lb - -

Technical Summary

Configuration - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc
Modes of Operation - Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow
Application - LV and MV ( 208V - 38 kV LV and MV ( 208V - 38 kV) 50 / 60 Hz

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 Per customer specification

Utility Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 Per customer specification

Environmental Parameters

Certifications - IBS, CBC, UBC & OSHPD Certified Per customer specification
Control Panel Enclosure - NEMA 1 or NEMA 3R, Freestanding Construction Per customer specification
Operating Temperature - 0 degrees to 50 degrees C Per customer specification
Storage Temperature - -20 degrees C to +60 degrees C Per customer specification
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 Per customer specification
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 Per customer specification
Add a Similar Product:
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQ425 Add