Compare Equipment Go Back

DE1000S GC
C280-16 Generator Set (Medium Speed)

Generator Set Specifications

Maximum Rating 1000 eKW 4000 ekW 4840 ekW (60Hz), 6500 kVA (50Hz)
Minimum Rating 1000 eKW 3150 ekW 4400 ekW (60Hz), 5875 kVA (50Hz)
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel, Tier 2 EPA Tier 4 Final, IMO Tier 2
Voltage 380 - 480 Volts 480 to 13800 Volts -
Frequency 60 Hz 60 Hz 50 / 60 Hz
Speed 1800 rpm 1800 rpm 900 / 1000 rpm
Duty Cycle Standby Standby, Mission Critical, Prime, Continuous Prime, Continuous
Standby Rating - 4000 (no fan)/3900/3620(no fan)/3500 ekW -
Prime Power Rating - 3600 (no fan)/3500/3300 (no fan)/3180 ekW -

Engine Specifications

Engine Model C32 TA, V-12, 4-Stroke Water-Cooled Diesel C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel C280-16, V-16,4-Stroke Water-Cooled Diesel
Bore 5.71 in 6.89 in 11 in
Stroke 6.38 in 8.66 in 11.8 in
Displacement 1958.86 in³ 6456.31 in³ 18032 in³
Compression Ratio 15.0:1 15.3:1 13:01
Aspiration TA Turbo Aftercooled TA
Fuel System EUI Common Rail Direct unit injection
Governor Type Adem™A4 ADEM� A4 Generator Set Monitoring System (GMS)

Generator Set Dimensions

Length - Minimum 164.3 in 261.5 in -
Length - Maximum 164.3 in 330.6 in 404 in
Width - Minimum 73.1 in 85.4 in -
Width - Maximum 73.1 in 127.7 in 99.62 in
Height - Minimum 87.3 in 87.6 in -
Height - Maximum 87.3 in 150.7 in 156.6 in
Dry Weight - Genset (minimum) 14669 lb 55100 lb -
Dry Weight - Genset (maximum) 14669 lb 66200 lb 141840 lb
Add a Similar Product:
  • 3616 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • 3606 Generator Set (Medium Speed) Add
  • C175-16 Generator Set Add