Compare Equipment Go Back

Cat Switchgear
MX350 Controller

Enclosure Rating

Configuration IP4X - -

Operating Temperature

Operating Temperature 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) - -

Dimensions

Standard Widths 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. - -
Standard Heights Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping - -
Standard Depths 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers - -

Technical Summary

Technical Summary Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. - -
Rating Range - Switch Dependent -
Transfer Type - Application Dependent -
Switch Type - Application Dependent -

Application

Application LV 380…480 VAC, 50 Hz, 3-Phase. - -

Modes of Operation

Modes of Operation Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. - -

Controller Specifications

Voltage Unbalance on Dropout for Source 1 and Source 2 - 5 to 20% of nominal -
Delay NeutralTransition Time Delays (DT,DW) - 0-10 minutes -
Control Power - 120 VAC -
Undervoltage Dropout for Source 1 and Source 2 - 75-99% of nominal -
Undervoltage Restore for Source 1 and Source 2 - 85-100% of nominal -
Overfrequency Dropout for Source 1 and Source 2 - 50.1 - 63 Hz -
Source Sensing - 120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A) -
Delay for Engine Cool Down (U) - 0-60 minutes -
Underfrequency Restore for Source 1 and Source 2 - 45 - 59.5 Hz -
Load Control Relay Contacts (2) - 0-259 minutes -
Overvoltage Dropout for Source 1 and Source 2 - 105 - 110% of nominal -
Voltage Unbalance for Restore for Source 1 and Source 2 - 4 to 19% of nominal -
Storage Temperature - (-40˚C - 90˚C ) -
Underfrequency Dropout for Source 1 and Source 2 - 45 - 59.9 Hz -
Overfrequency Restore for Source 1 and Source 2 - 50 - 62.9 Hz -
Delay Transfer to Nonpreferred Source (W) - 0-5 minutes -
Operating Temperature Ambient - (-20˚C to 50˚C) -
Communications Interface - Optional - Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T) -
Overvoltage Restore for Source 1 and Source 2 - 103 - 108% of nominal -
Load Control Relay Contacts (1) - rated for 10A @ 24VDC or 120VAC -
Add a Similar Product:
  • MX150 Microprocessor Controller Add
  • MX250 Microprocessor Controller Add
  • CTS Series Automatic Transfer Switch Add
  • CTSM and CTGM Series Manual Transfer Switches Add
  • CTX Series Automatic Transfer Switch Add
  • CTG Series Automatic Transfer Switch Add
  • CTGSE & CTGDSE Series Service Rated Entrance Rated Automatic Transfer Switch Add
  • Cat Customizable Switchgear and Controls Add
  • CTE Series Automatic Transfer Switch Add