Cat Switchgear |
|
|
|
Enclosure Rating |
|||
---|---|---|---|
Configuration | IP4X | - | - |
Operating Temperature |
|||
Operating Temperature | 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) | - | - |
Dimensions |
|||
Standard Widths | 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. | - | - |
Standard Heights | Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping | - | - |
Standard Depths | 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers | - | - |
Technical Summary |
|||
Technical Summary | Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. | - | - |
Application |
|||
Application | LV 380…480 VAC, 50 Hz, 3-Phase. | - | - |
Modes of Operation |
|||
Modes of Operation | Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. | - | - |