Compare Equipment Go Back
Cat Switchgear |
Cat EGP Switchgear |
Cat XLM Switchgear |
|
Enclosure Rating |
|||
---|---|---|---|
Configuration | IP4X | - | - |
Operating Temperature |
|||
Operating Temperature | 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) | - | - |
Dimensions |
|||
Standard Widths | 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. | - | - |
Standard Heights | Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping | - | - |
Standard Depths | 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers | - | - |
Technical Summary |
|||
Technical Summary | Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. | - | - |
Configuration | - | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications |
Modes of Operation | - | Multi-unit Island and multi-unit standby mode with optional redundant controls and components. | Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power |
Application | - | LV and MV (208V - 38 kV) | LV and MV ( 208V - 38 kV |
Application |
|||
Application | LV 380…480 VAC, 50 Hz, 3-Phase. | - | - |
Modes of Operation |
|||
Modes of Operation | Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. | - | - |
Generator Protective Devices |
|||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 |
Environmental Parameters |
|||
Certifications | - | IBC, CBC, UBC & OSHPD Certified | IBS, CBC, UBC & OSHPD Certified |
Control Panel Enclosure | - | NEMA 1 or NEMA 3R Freestanding Construction | NEMA 1 or NEMA 3R, Freestanding Construction |
Operating Temperature | - | 0°C to 50°C | 0 degrees to 50 degrees C |
Storage Temperature | - | -20°C to +60°C | -20 degrees C to +60 degrees C |
Low Voltage Standards | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 |
Medium Voltage Standards | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 |
Utility Protective Devices |
|||
ANSI Protective Devices | - | - | 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 |
Add a Similar Product:
- Cat Customizable Switchgear and Controls Add
- EMCP 4.4 Master Control Panel Add
- Engine Paralleling and Integration Control (EPIC) Add
- Energy Capacity Expansion (ECE) module Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
- Temporary Connection Boxes Add
- Energy Time Shift (ETS) Module Add
- XQ425 Add
- XQP550 EU Stage V Add