Cat Customizable Switchgear and Controls
Cat XLM Switchgear
Cat Switchgear

Technical Summary

Configuration Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications -
Modes of Operation All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power -
Application LV and MV ( 208V - 38 kV) 50 / 60 Hz LV and MV ( 208V - 38 kV -
Technical Summary - - Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers.

Generator Protective Devices

ANSI Protective Devices Per customer specification 15/25, 27/59, 81 O/U, 32, 40, 50, 51 -

Utility Protective Devices

ANSI Protective Devices Per customer specification 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 -

Environmental Parameters

Certifications Per customer specification IBS, CBC, UBC & OSHPD Certified -
Control Panel Enclosure Per customer specification NEMA 1 or NEMA 3R, Freestanding Construction -
Operating Temperature Per customer specification 0 degrees to 50 degrees C -
Storage Temperature Per customer specification -20 degrees C to +60 degrees C -
Low Voltage Standards Per customer specification NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 -
Medium Voltage Standards Per customer specification NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 -

Enclosure Rating

Configuration - - IP4X

Operating Temperature

Operating Temperature - - 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F)

Dimensions

Standard Widths - - 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A.
Standard Heights - - Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping
Standard Depths - - 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers

Application

Application - - LV 380…480 VAC, 50 Hz, 3-Phase.

Modes of Operation

Modes of Operation - - Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc.
Add a Similar Product:
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQ425 Add
  • XQP550 EU Stage V Add