Compare Equipment Go Back

Cat XLM Switchgear
Energy Time Shift (ETS) Module
XQ570 Tier 4 Final - 455 ekW (568 kVA)

Technical Summary

Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications - -
Modes of Operation Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power - -
Application LV and MV ( 208V - 38 kV Peak Shaving -
Module Type - Energy Time Shift -
Nameplate Power - 570 kW | 1000 kW -
Nameplate Energy Capacity - 1518 kWh -

Generator Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51 - -

Utility Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 - -

Environmental Parameters

Certifications IBS, CBC, UBC & OSHPD Certified - -
Control Panel Enclosure NEMA 1 or NEMA 3R, Freestanding Construction - -
Operating Temperature 0 degrees to 50 degrees C - -
Storage Temperature -20 degrees C to +60 degrees C - -
Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 - -
Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 - -

Generator Set

Rating Prime - - 455 ekW (568 kVA)
Frequency - - 60 Hz
Voltage - - 120 - 600 V
Rating Standby - - 500 ekW (625 kVA)

Engine

Engine - - Cat C18
Fuel - - Diesel

Dimensions

Height - Without Trailer - - 102 in
Length - Without Trailer - - 240 in
Width - Without Trailer - - 96 in
Weight with Lube Oil and Coolant, Without Trailer - - 24125 lb

Fuel Consumption

100% Load 60Hz - - 35.9 gal/hr
75% Load 60Hz - - 28.3 gal/hr
50% Load 60Hz - - 20.5 gal/hr

Noise rating (with enclosure)

Sound Power @ 7 meters (23 feet) @ All Ratings - - 74 dB(A)
Add a Similar Product:
  • Cat Switchgear Add
  • Cat Customizable Switchgear and Controls Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add
  • XQ230 Rental Power Add