Compare Equipment Go Back

Cat XLM Switchgear
XQ570 Tier 4 Final - 455 ekW (568 kVA)

Technical Summary

Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications - -
Modes of Operation Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power - -
Application LV and MV ( 208V - 38 kV - -

Generator Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51 - -

Utility Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 - -

Environmental Parameters

Certifications IBS, CBC, UBC & OSHPD Certified - -
Control Panel Enclosure NEMA 1 or NEMA 3R, Freestanding Construction - -
Operating Temperature 0 degrees to 50 degrees C - -
Storage Temperature -20 degrees C to +60 degrees C - -
Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 - -
Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 - -

Generator Set

Rating Prime - 455 ekW (568 kVA) -
Frequency - 60 Hz -
Voltage - 120 - 600 V -
Rating Standby - 500 ekW (625 kVA) -

Engine

Engine - Cat C18 -
Fuel - Diesel -

Dimensions

Height - Without Trailer - 102 in -
Length - Without Trailer - 240 in -
Width - Without Trailer - 96 in -
Weight with Lube Oil and Coolant, Without Trailer - 24125 lb -

Fuel Consumption

100% Load 60Hz - 35.9 gal/hr -
75% Load 60Hz - 28.3 gal/hr -
50% Load 60Hz - 20.5 gal/hr -

Noise rating (with enclosure)

Sound Power @ 7 meters (23 feet) @ All Ratings - 74 dB(A) -
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Temporary Connection Boxes Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • XQP550 EU Stage V Add