Cat EGP Switchgear |
Cat Switchgear |
|
|
Technical Summary |
|||
---|---|---|---|
Configuration | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications | - | - |
Modes of Operation | Multi-unit Island and multi-unit standby mode with optional redundant controls and components. | - | - |
Application | LV and MV (208V - 38 kV) | - | - |
Technical Summary | - | Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. | - |
Generator Protective Devices |
|||
ANSI Protective Devices | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | - | - |
Environmental Parameters |
|||
Certifications | IBC, CBC, UBC & OSHPD Certified | - | - |
Control Panel Enclosure | NEMA 1 or NEMA 3R Freestanding Construction | - | - |
Operating Temperature | 0°C to 50°C | - | - |
Storage Temperature | -20°C to +60°C | - | - |
Low Voltage Standards | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - | - |
Medium Voltage Standards | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - | - |
Enclosure Rating |
|||
Configuration | - | IP4X | - |
Operating Temperature |
|||
Operating Temperature | - | 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) | - |
Dimensions |
|||
Standard Widths | - | 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. | - |
Standard Heights | - | Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping | - |
Standard Depths | - | 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers | - |
Application |
|||
Application | - | LV 380…480 VAC, 50 Hz, 3-Phase. | - |
Modes of Operation |
|||
Modes of Operation | - | Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. | - |
Add a Similar Product:
- Cat XLM Switchgear Add
- Cat Customizable Switchgear and Controls Add
- Engine Paralleling and Integration Control (EPIC) Add
- EMCP 4.4 Master Control Panel Add
- Energy Time Shift (ETS) Module Add
- Energy Capacity Expansion (ECE) module Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
- Temporary Connection Boxes Add
- XQ230 Rental Power Add