Compare Equipment Go Back

Cat EGP Switchgear
DE800S GC
Cat Switchgear

Technical Summary

Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications - -
Modes of Operation Multi-unit Island and multi-unit standby mode with optional redundant controls and components. - -
Application LV and MV (208V - 38 kV) - -
Technical Summary - - Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers.

Generator Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51 - -

Environmental Parameters

Certifications IBC, CBC, UBC & OSHPD Certified - -
Control Panel Enclosure NEMA 1 or NEMA 3R Freestanding Construction - -
Operating Temperature 0°C to 50°C - -
Storage Temperature -20°C to +60°C - -
Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 - -
Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 - -

Generator Set Specifications

Minimum Rating - 800 eKW -
Maximum Rating - 800 eKW -
Emissions/Fuel Strategy - Low Fuel Consumption -
Voltage - 380 - 480 Volts -
Frequency - 60 Hz -
Speed - 1800 rpm -
Duty Cycle - Standby -

Engine Specifications

Engine Model - C27 TA, V-12, 4-Stroke Water-Cooled Diesel -
Bore - 5.4 in -
Stroke - 6 in -
Displacement - 1649.47 in³ -
Compression Ratio - 16.5:1 -
Aspiration - TA -
Fuel System - MEUI -
Governor Type - Adem™A4 -

Generator Set Dimensions

Length - Minimum - 164.3 in -
Length - Maximum - 164.3 in -
Width - Minimum - 73.1 in -
Width - Maximum - 73.1 in -
Height - Minimum - 87.3 in -
Height - Maximum - 87.3 in -
Dry Weight - Genset (minimum) - 13695 lb -
Dry Weight - Genset (maximum) - 13695 lb -

Enclosure Rating

Configuration - - IP4X

Operating Temperature

Operating Temperature - - 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F)

Dimensions

Standard Widths - - 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A.
Standard Heights - - Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping
Standard Depths - - 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers

Application

Application - - LV 380…480 VAC, 50 Hz, 3-Phase.

Modes of Operation

Modes of Operation - - Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc.
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat XLM Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add