Compare Equipment Go Back

Engine Paralleling and Integration Control (EPIC)
Cat Switchgear
XQ570 Tier 4 Final - 455 ekW (568 kVA)

Technical Summary

Configuration Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) - -
Modes of Operation Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) - -
Application LV and MV (208V-27kV) - -
Technical Summary - Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. -

Generator Protective Devices

ANSI Protective Devices 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) - -

Utility Protective Devices

ANSI Protective Devices 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) - -

Environmental Parameters

Certifications UL / cUL 508A - -
Control Panel Enclosure NEMA 12 - -
Operating Temperature 0°C to 55°C - -
Storage Temperature -20°C to 60°C - -

Enclosure Rating

Configuration - IP4X -

Operating Temperature

Operating Temperature - 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) -

Dimensions

Standard Widths - 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. -
Standard Heights - Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping -
Standard Depths - 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers -
Height - Without Trailer - - 102 in
Length - Without Trailer - - 240 in
Width - Without Trailer - - 96 in
Weight with Lube Oil and Coolant, Without Trailer - - 24125 lb

Application

Application - LV 380…480 VAC, 50 Hz, 3-Phase. -

Modes of Operation

Modes of Operation - Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. -

Generator Set

Rating Prime - - 455 ekW (568 kVA)
Frequency - - 60 Hz
Voltage - - 120 - 600 V
Rating Standby - - 500 ekW (625 kVA)

Engine

Engine - - Cat C18
Fuel - - Diesel

Fuel Consumption

100% Load 60Hz - - 35.9 gal/hr
75% Load 60Hz - - 28.3 gal/hr
50% Load 60Hz - - 20.5 gal/hr

Noise rating (with enclosure)

Sound Power @ 7 meters (23 feet) @ All Ratings - - 74 dB(A)
Add a Similar Product:
  • Cat XLM Switchgear Add
  • Cat Customizable Switchgear and Controls Add
  • EMCP 4.4 Master Control Panel Add
  • Cat EGP Switchgear Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add
  • XQ425 Add