XQ35 |
Cat Switchgear |
Cat EGP Switchgear |
|
Generator Set |
|||
---|---|---|---|
Rating Prime | 27 ekW (35 kVA) | - | - |
Frequency | 60 Hz | - | - |
Voltage | 120 - 600 V | - | - |
Rating Standby | 30 ekW (38 kVA) | - | - |
Engine |
|||
Engine | Cat C2.2 | - | - |
Fuel | Diesel | - | - |
Dimensions |
|||
Height - Without Trailer | 63.7 in | - | - |
Length - Without Trailer | 91.3 in | - | - |
Width - Without Trailer | 41.4 in | - | - |
Weight with Lube Oil and Coolant, Without Trailer | 2215 lb | - | - |
Standard Widths | - | 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. | - |
Standard Heights | - | Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping | - |
Standard Depths | - | 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers | - |
Fuel Consumption |
|||
100% Load 60Hz | 2.6 gal/hr | - | - |
75% Load 60Hz | 2 gal/hr | - | - |
50% Load 60Hz | 1.3 gal/hr | - | - |
Noise rating (with enclosure) |
|||
Sound Power @ 7 meters (23 feet) @ All Ratings | 63 dB(A) | - | - |
Enclosure Rating |
|||
Configuration | - | IP4X | - |
Operating Temperature |
|||
Operating Temperature | - | 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) | - |
Technical Summary |
|||
Technical Summary | - | Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. | - |
Configuration | - | - | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications |
Modes of Operation | - | - | Multi-unit Island and multi-unit standby mode with optional redundant controls and components. |
Application | - | - | LV and MV (208V - 38 kV) |
Application |
|||
Application | - | LV 380…480 VAC, 50 Hz, 3-Phase. | - |
Modes of Operation |
|||
Modes of Operation | - | Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. | - |
Generator Protective Devices |
|||
ANSI Protective Devices | - | - | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 |
Environmental Parameters |
|||
Certifications | - | - | IBC, CBC, UBC & OSHPD Certified |
Control Panel Enclosure | - | - | NEMA 1 or NEMA 3R Freestanding Construction |
Operating Temperature | - | - | 0°C to 50°C |
Storage Temperature | - | - | -20°C to +60°C |
Low Voltage Standards | - | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 |
Medium Voltage Standards | - | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 |
Add a Similar Product:
-
Cat Customizable Switchgear and Controls Add
-
Cat XLM Switchgear Add
-
Engine Paralleling and Integration Control (EPIC) Add
-
EMCP 4.4 Master Control Panel Add
-
Energy Capacity Expansion (ECE) module Add
-
Cat® BDP1000 Bi-Directional Power Inverter Add
-
Temporary Connection Boxes Add
-
Energy Time Shift (ETS) Module Add
-
XQ425 Add
-
XQ570 Tier 4 Final – 455 ekW (568 kVA) Add