Compare Equipment Go Back
Cat G3520H Combined Heat and Power (CHP) Solution |
Cat XLM Switchgear |
EMCP 4.4 Master Control Panel |
|
Generator Set Specifications |
|||
---|---|---|---|
Continuous Rating | 2480 ekW @ 1.0pf | - | - |
Fuel Type | Natural Gas | - | - |
Maximum Electrical Efficiency | 42.40% | - | - |
Frequency | 60 Hz | - | - |
RPM | 1500 | - | - |
Engine Specifications |
|||
Engine Model | G3520H | - | - |
Displacement | 5956 in³ | - | - |
Aspiration | TA | - | - |
Bore | 6.7 in | - | - |
Stroke | 8.5 in | - | - |
Fuel System | Electronic Fuel Control Valve | - | - |
Governor Type | ADEM™ A4 | - | - |
Compression Ratio | 11.1 | - | - |
Generator Set Dimensions |
|||
Length | 302 in | - | - |
Width | 86 in | - | - |
Height | 97 in | - | - |
Dry Weight - Genset | 54675 lb | - | - |
Weight | 168000 lb | - | - |
Technical Summary |
|||
Configuration | - | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications | Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. |
Modes of Operation | - | Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power | Emergency standby, island, utility paralleling |
Application | - | LV and MV ( 208V - 38 kV | LV and MV (208V - 38 kV) |
Generator Protective Devices |
|||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 |
Utility Protective Devices |
|||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) |
Environmental Parameters |
|||
Certifications | - | IBS, CBC, UBC & OSHPD Certified | IBC, CBC, UBC & OSHPD Certified |
Control Panel Enclosure | - | NEMA 1 or NEMA 3R, Freestanding Construction | NEMA 1 wall-mounted construction |
Operating Temperature | - | 0 degrees to 50 degrees C | 0°C to 50°C |
Storage Temperature | - | -20 degrees C to +60 degrees C | -20°C to +60°C |
Low Voltage Standards | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 |
Medium Voltage Standards | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 |
Add a Similar Product:
- Cat Switchgear Add
- Cat Customizable Switchgear and Controls Add
- Cat EGP Switchgear Add
- Engine Paralleling and Integration Control (EPIC) Add
- Energy Capacity Expansion (ECE) module Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- Temporary Connection Boxes Add
- Energy Time Shift (ETS) Module Add
- XQ425 Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add