Compare Equipment Go Back

Cat G3520H Combined Heat and Power (CHP) Solution
Energy Time Shift (ETS) Module
EMCP 4.4 Master Control Panel

Generator Set Specifications

Continuous Rating 2480 ekW @ 1.0pf - -
Fuel Type Natural Gas - -
Maximum Electrical Efficiency 42.40% - -
Frequency 60 Hz - -
RPM 1500 - -

Engine Specifications

Engine Model G3520H - -
Displacement 5956 in³ - -
Aspiration TA - -
Bore 6.7 in - -
Stroke 8.5 in - -
Fuel System Electronic Fuel Control Valve - -
Governor Type ADEM™ A4 - -
Compression Ratio 11.1 - -

Generator Set Dimensions

Length 302 in - -
Width 86 in - -
Height 97 in - -
Dry Weight - Genset 54675 lb - -
Weight 168000 lb - -

Technical Summary

Application - Peak Shaving LV and MV (208V - 38 kV)
Module Type - Energy Time Shift -
Nameplate Power - 570 kW | 1000 kW -
Nameplate Energy Capacity - 1518 kWh -
Configuration - - Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source.
Modes of Operation - - Emergency standby, island, utility paralleling

Generator Protective Devices

ANSI Protective Devices - - 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices - - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications - - IBC, CBC, UBC & OSHPD Certified
Control Panel Enclosure - - NEMA 1 wall-mounted construction
Operating Temperature - - 0°C to 50°C
Storage Temperature - - -20°C to +60°C
Low Voltage Standards - - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Add a Similar Product:
  • Cat Switchgear Add
  • Cat Customizable Switchgear and Controls Add
  • Cat XLM Switchgear Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add