Compare Equipment Go Back

G3516C Gas Generator Set
Cat Switchgear
Cat XLM Switchgear
EMCP 4.4 Master Control Panel

Generator Set Specifications

Continuous Rating 1660 ekW - - -
Fuel Type Natural Gas - - -
Maximum Electrical Efficiency 37.70% - - -
Maximum Standby Rating 1500 - - -
Frequency 50 / 60 Hz - - -
RPM 1500/1800 - - -

Engine Specifications

Engine Model G3516C - - -
Displacement 4210 in³ - - -
Aspiration TA - - -
Bore 6.7 in - - -
Stroke 7.5 in - - -

Generator Set Dimensions

Length 219 in - - -
Width 72 in - - -
Height 92 in - - -
Dry Weight - Genset 31226 lb - - -

Enclosure Rating

Configuration - IP4X - -

Operating Temperature

Operating Temperature - 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) - -

Dimensions

Standard Widths - 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. - -
Standard Heights - Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping - -
Standard Depths - 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers - -

Technical Summary

Technical Summary - Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. - -
Configuration - - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source.
Modes of Operation - - Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power Emergency standby, island, utility paralleling
Application - - LV and MV ( 208V - 38 kV LV and MV (208V - 38 kV)

Application

Application - LV 380…480 VAC, 50 Hz, 3-Phase. - -

Modes of Operation

Modes of Operation - Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. - -

Generator Protective Devices

ANSI Protective Devices - - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices - - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications - - IBS, CBC, UBC & OSHPD Certified IBC, CBC, UBC & OSHPD Certified
Control Panel Enclosure - - NEMA 1 or NEMA 3R, Freestanding Construction NEMA 1 wall-mounted construction
Operating Temperature - - 0 degrees to 50 degrees C 0°C to 50°C
Storage Temperature - - -20 degrees C to +60 degrees C -20°C to +60°C
Low Voltage Standards - - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • Temporary Connection Boxes Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add
  • XQ125 Rental Power Add