Gas Generator G3512H
Cat Switchgear
Engine Paralleling and Integration Control (EPIC)
Energy Capacity Expansion (ECE) module

Generator Set Specifications

Continuous Rating 1515 ekW / 1505 ekW @1.0pf - - -
Fuel Type Natural Gas, Hydrogen Blend (up to 25%) - - -
Maximum Electrical Efficiency 44.90% - - -
Frequency 50 / 60 Hz - - -
RPM 1500 rpm - - -

Engine Specifications

Engine Model G3512H - - -
Displacement 3574 in³ - - -
Aspiration TA - - -
Bore 6.7 in - - -
Stroke 8.5 in - - -
Governor Type ADEM A4 - - -

Generator Set Dimensions

Length 223 in - - -
Width 76 in - - -
Height 91 in - - -
Dry Weight - Genset 31085 lb - - -

Enclosure Rating

Configuration - IP4X - -

Operating Temperature

Operating Temperature - 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) - -

Dimensions

Standard Widths - 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. - -
Standard Heights - Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping - -
Standard Depths - 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers - -

Technical Summary

Technical Summary - Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. - -
Configuration - - Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) -
Modes of Operation - - Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) -
Application - - LV and MV (208V-27kV) Reserve Power Capacity
Module Type - - - Energy Storage
Nameplate Energy Capacity - - - 1518 kWh - 7590 kWh

Application

Application - LV 380…480 VAC, 50 Hz, 3-Phase. - -

Modes of Operation

Modes of Operation - Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. - -

Generator Protective Devices

ANSI Protective Devices - - 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) -

Utility Protective Devices

ANSI Protective Devices - - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) -

Environmental Parameters

Certifications - - UL / cUL 508A -
Control Panel Enclosure - - NEMA 12 -
Operating Temperature - - 0°C to 55°C -
Storage Temperature - - -20°C to 60°C -
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat XLM Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Cat EGP Switchgear Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • Temporary Connection Boxes Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add
  • XQ425 Add