Compare Equipment Go Back

G3512 1000kW Gas Generator Set
Cat XLM Switchgear
Cat Switchgear
Cat EGP Switchgear

Generator Set Specifications

Gas Standby Rating 1000 ekW @ 0.8pf - - -
Fuel Type Natural Gas, Hydrogen Blend (up to 5%) - - -
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Stationary Genset - - -
RPM 1800 rpm - - -
Frequency 60 Hz - - -
Compression Ratio 9.7 - - -
Displacement 3173 in³ - - -

Engine Specifications

Engine Model G3512 - - -
Displacement 3173 in³ - - -
Aspiration TA - - -
Bore 6.7 in - - -
Stroke 7.5 in - - -

Generator Set Dimensions

Length 205.7 in - - -
Width 90 in - - -
Height 99.4 in - - -
Weight 27500 lb - - -

Technical Summary

Configuration - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
Modes of Operation - Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power - Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
Application - LV and MV ( 208V - 38 kV - LV and MV (208V - 38 kV)
Technical Summary - - Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. -

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 - 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 - -

Environmental Parameters

Certifications - IBS, CBC, UBC & OSHPD Certified - IBC, CBC, UBC & OSHPD Certified
Control Panel Enclosure - NEMA 1 or NEMA 3R, Freestanding Construction - NEMA 1 or NEMA 3R Freestanding Construction
Operating Temperature - 0 degrees to 50 degrees C - 0°C to 50°C
Storage Temperature - -20 degrees C to +60 degrees C - -20°C to +60°C
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110

Enclosure Rating

Configuration - - IP4X -

Operating Temperature

Operating Temperature - - 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) -

Dimensions

Standard Widths - - 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. -
Standard Heights - - Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping -
Standard Depths - - 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers -

Application

Application - - LV 380…480 VAC, 50 Hz, 3-Phase. -

Modes of Operation

Modes of Operation - - Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. -
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add
  • XQ425 Add