Compare Equipment Go Back

G3512 750kW Gas Generator Set
Cat Customizable Switchgear and Controls
Cat Switchgear
Cat XLM Switchgear

Generator Set Specifications

Gas Standby Rating 750 ekW @ 0.8pf - - -
Fuel Type Natural Gas, Hydrogen Blend (up to 5%) - - -
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Stationary Genset - - -
RPM 1800 rpm - - -
Frequency 60 Hz - - -
Displacement 3173 in³ - - -

Engine Specifications

Engine Model G3512 - - -
Displacement 3173 in³ - - -
Aspiration TA - - -
Bore 6.7 in - - -
Stroke 7.5 in - - -
Governor Type ADEM A4 - - -

Generator Set Dimensions

Length 205.7 in - - -
Width 90 in - - -
Height 99.4 in - - -
Weight 27500 lb - - -

Technical Summary

Configuration - Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation - All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow - Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application - LV and MV ( 208V - 38 kV) 50 / 60 Hz - LV and MV ( 208V - 38 kV
Technical Summary - - Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. -

Generator Protective Devices

ANSI Protective Devices - Per customer specification - 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices - Per customer specification - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

Environmental Parameters

Certifications - Per customer specification - IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure - Per customer specification - NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature - Per customer specification - 0 degrees to 50 degrees C
Storage Temperature - Per customer specification - -20 degrees C to +60 degrees C
Low Voltage Standards - Per customer specification - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - Per customer specification - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110

Enclosure Rating

Configuration - - IP4X -

Operating Temperature

Operating Temperature - - 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) -

Dimensions

Standard Widths - - 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. -
Standard Heights - - Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping -
Standard Depths - - 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers -

Application

Application - - LV 380…480 VAC, 50 Hz, 3-Phase. -

Modes of Operation

Modes of Operation - - Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. -
Add a Similar Product:
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • EMCP 4.4 Master Control Panel Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Temporary Connection Boxes Add
  • XQ425 Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add