Compare Equipment Go Back

DG175-2 (Single-phase)
Cat Switchgear
Engine Paralleling and Integration Control (EPIC)
Cat XLM Switchgear

Generator Set Specifications

Frequency 60 Hz - - -
Natural Gas Rating 175 ekW - - -
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Application - - -
Displacement 864.71 in - - -
Fuel Type Natural Gas - - -
Speed 1800 rpm - - -

Engine Specifications

Engine Model G14.2L Inline 6, 4 cycle, Spark Ignited - - -
Fuel System Carburetor, Down Draft - - -
Aspiration Turbocharged - Aftercooled - - -
Governor Type Electronic - - -
Compression Ratio 9.5:1 - - -
Bore 5.31 in - - -
Stroke 6.5 in - - -

Generator Set Dimensions

Length 127.95 in - - -
Width 52.93 in - - -
Height 67.37 in - - -
Weight 5756 lb - - -

Enclosure Rating

Configuration - IP4X - -

Operating Temperature

Operating Temperature - 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) - -

Dimensions

Standard Widths - 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. - -
Standard Heights - Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping - -
Standard Depths - 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers - -

Technical Summary

Technical Summary - Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. - -
Configuration - - Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation - - Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application - - LV and MV (208V-27kV) LV and MV ( 208V - 38 kV

Application

Application - LV 380…480 VAC, 50 Hz, 3-Phase. - -

Modes of Operation

Modes of Operation - Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. - -

Generator Protective Devices

ANSI Protective Devices - - 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices - - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

Environmental Parameters

Certifications - - UL / cUL 508A IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure - - NEMA 12 NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature - - 0°C to 55°C 0 degrees to 50 degrees C
Storage Temperature - - -20°C to 60°C -20 degrees C to +60 degrees C
Low Voltage Standards - - - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - - - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • EMCP 4.4 Master Control Panel Add
  • Cat EGP Switchgear Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Temporary Connection Boxes Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add
  • XQ425 Add