Compare Equipment Go Back

C175-20
C280-16 Generator Set (Medium Speed)

Generator Set Specifications

Standby Rating 4000 (no fan)/3900/3620(no fan)/3500 ekW - -
Prime Power Rating 3600 (no fan)/3500/3300 (no fan)/3180 ekW - -
Emissions/Fuel Strategy Low Fuel, Tier 2 EPA Tier 4 Final, IMO Tier 2 -
Voltage 480 to 13800 Volts - -
Frequency 60 Hz 50 / 60 Hz -
Speed 1800 rpm 900 / 1000 rpm -
Duty Cycle Standby, Mission Critical, Prime, Continuous Prime, Continuous -
Maximum Rating 4000 ekW 4840 ekW (60Hz), 6500 kVA (50Hz) -
Minimum Rating 3150 ekW 4400 ekW (60Hz), 5875 kVA (50Hz) -

Engine Specifications

Engine Model C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel C280-16, V-16,4-Stroke Water-Cooled Diesel -
Bore 6.89 in 11 in -
Stroke 8.66 in 11.8 in -
Displacement 6456.31 in³ 18032 in³ -
Compression Ratio 15.3:1 13:01 -
Aspiration Turbo Aftercooled TA -
Fuel System Common Rail Direct unit injection -
Governor Type ADEM� A4 Generator Set Monitoring System (GMS) -

Generator Set Dimensions

Length - Minimum 261.5 in - -
Length - Maximum 330.6 in 404 in -
Width - Minimum 85.4 in - -
Width - Maximum 127.7 in 99.62 in -
Height - Minimum 87.6 in - -
Height - Maximum 150.7 in 156.6 in -
Dry Weight - Genset (minimum) 55100 lb - -
Dry Weight - Genset (maximum) 66200 lb 141840 lb -
Add a Similar Product:
  • 3616 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3606 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • C175-16 Tier 4 Final Add