Compare Equipment Go Back

DE88E0 (50 Hz) Generator Set
C280-6 Generator Set (Medium Speed)
C175-16 Generator Set
C280-16 Generator Set (Medium Speed)

Generator Set Specifications

Minimum Rating 80 kVA 1650 ekW (60Hz), 2200 kVA (50Hz) 3150 ekW 2500 ekW 4400 ekW (60Hz), 5875 kVA (50Hz)
Maximum Rating 88 kVA 1820 ekW (60Hz), 2425 kVA (50Hz) 4000 ekW 3365 ekW 4840 ekW (60Hz), 6500 kVA (50Hz)
Emissions/Fuel Strategy Non Regulated IMO Tier 2 Low Fuel, Tier 2 Low Fuel, Tier 2 EPA Tier 4 Final, IMO Tier 2
Voltage 220 to 415 Volts - 480 to 13800 Volts 480 to 13800 Volts -
Frequency 50 Hz 50 / 60 Hz 60 Hz 60 Hz 50 / 60 Hz
Speed 1500 rpm 900 / 1000 rpm 1800 rpm 1800 RPM 900 / 1000 rpm
Duty Cycle Standby, Prime Prime, Continuous Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime, Continuous Prime, Continuous
Standby Rating - - 4000 (no fan)/3900/3620(no fan)/3500 ekW 3365(no fan)/3250/3100(no fan)/3000 ekW -
Prime Power Rating - - 3600 (no fan)/3500/3300 (no fan)/3180 ekW 3115(no fan)/3000/2825(no fan)/2725 ekW -

Engine Specifications

Engine Model Cat® C4.4 C280-6, I-6,4-Stroke Water-Cooled Diesel C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel C280-16, V-16,4-Stroke Water-Cooled Diesel
Bore 4.1 in 11 in 6.89 in 6.89 in 11 in
Stroke 5 in 11.8 in 8.66 in 8.66 in 11.8 in
Displacement 201.4 in³ 111 in³ 6456.31 in³ 6456.31 in³ 18032 in³
Compression Ratio 17.25:1 13:01 15.3:1 16.7:1 13:01
Aspiration Turbocharged TA Turbo Aftercooled Turbo Aftercooled TA
Fuel System Inline Direct unit injection Common Rail Common Rail Direct unit injection
Governor Type Mechanical Generator Set Monitoring System (GMS) ADEM� A4 ADEM� A4 Generator Set Monitoring System (GMS)

Generator Set Dimensions

Length - Maximum 75.8 in 404 in 331.1 in 330.6 in 404 in
Width - Maximum 44.1 in 99.62 in 128.5 in 124.3 in 99.62 in
Height - Maximum 53.6 in 156.6 in 150.7 in 134.2 in 156.6 in
Dry Weight - Genset (maximum) 2332 lb 74970 lb 66200 lb 57774 lb 141840 lb
Length - Minimum - - 262.5 in 250.9 in -
Width - Minimum - - 92 in 82.7 in -
Height - Minimum - - 99.8 in 86.9 in -
Dry Weight - Genset (minimum) - - 55100 lb 42750 lb -
Add a Similar Product:
  • 3616 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3606 Generator Set (Medium Speed) Add
  • C175-16 Tier 4 Final Add
  • 3516E Low Voltage Generator Set Add