C18 | DE850E0 50Hz LOW BSFC
C175-16 Tier 4 Final
C280-16 Generator Set (Medium Speed)

Generator Set Specifications

Minimum Rating 770 kVA 2500 ekW 4400 ekW (60Hz), 5875 kVA (50Hz)
Maximum Rating 850 kVA 3100 ekW 4840 ekW (60Hz), 6500 kVA (50Hz)
Emissions/Fuel Strategy Non Regulated U.S. EPA Certified Tier 4 EPA Tier 4 Final, IMO Tier 2
Voltage 200 to 400 Volts 480 to 13800 Volts -
Frequency 50 Hz 60 Hz 50 / 60 Hz
Duty Cycle Standby, Prime Standby, Mission Critical, Prime, Continuous Prime, Continuous
Standby Rating - 3100(no fan)/3000 ekW -
Prime Power Rating - 2825(no fan)/2725 ekW -
Speed - 1800 rpm 900 / 1000 rpm

Engine Specifications

Aspiration Turbocharged, Air to Air Aftercooled Turbo Aftercooled TA
Engine Model - C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel C280-16, V-16,4-Stroke Water-Cooled Diesel
Bore - 6.89 in 11 in
Stroke - 8.66 in 11.8 in
Displacement - 5155.88 in³ 18032 in³
Compression Ratio - 16.7:1 13:01
Fuel System - EUI Direct unit injection
Governor Type - ADEM� A4 Generator Set Monitoring System (GMS)

Generator Set Dimensions

Length - Minimum - 242.77 in -
Length - Maximum - 320 in 404 in
Width - Minimum - 82.7 in -
Width - Maximum - 122.8 in 99.62 in
Height - Minimum - 127.2 in -
Height - Maximum - 142.3 in 156.6 in
Dry Weight - Genset (minimum) - 42750 lb -
Dry Weight - Genset (maximum) - 45114 lb 141840 lb
Add a Similar Product:
  • 3616 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • 3606 Generator Set (Medium Speed) Add
  • C175-20 Add