Compare Equipment Go Back

3512B Diesel Generator Set
3608 Generator Set (Medium Speed)
C280-16 Generator Set (Medium Speed)
C280-6 Generator Set (Medium Speed)
C280-8 Generator Set (Medium Speed)
3516E Generator Set

Generator Set Specifications

Standby Rating 1875/1750 kVA - - - - 3500/3250/3000 kVA 4000 (no fan)/3900/3620(no fan)/3500 ekW
Prime Power Rating 1700/1600 kVA - - - - 3175/2950/2725 kVA 3600 (no fan)/3500/3300 (no fan)/3180 ekW
Emissions/Fuel Strategy Low Fuel , Low Emissions Low Fuel Consumption EPA Tier 4 Final, IMO Tier 2 IMO Tier 2 EPA Tier 4 Final, IMO Tier 2 U.S. EPA Cert. Tier 2 / Low NOx Low Fuel, Tier 2
Voltage 400 to 415 Volts - - - - 380 to 11000 volts 480 to 13800 Volts
Frequency 50 Hz 50 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 Hz 60 Hz
Speed 1500 rpm 750 & 1000 rpm 900 / 1000 rpm 900 / 1000 rpm 900 / 1000 rpm 1500 rpm 1800 rpm
Duty Cycle Standby, Mission Critical, Prime, Continuous Standby, Prime, Continuous Prime, Continuous Prime, Continuous Prime, Continuous Standby, Mission Critical, Prime Standby, Mission Critical, Prime, Continuous
Minimum Rating 1600 kVA 2363 kVA 4400 ekW (60Hz), 5875 kVA (50Hz) 1650 ekW (60Hz), 2200 kVA (50Hz) 2200 ekW (60Hz), 2938 kVA (50Hz) 2725 kVA 3150 ekW
Maximum Rating 1875 kVA 3575 kVA 4840 ekW (60Hz), 6500 kVA (50Hz) 1820 ekW (60Hz), 2425 kVA (50Hz) 2420 ekW (60Hz), 3250 kVA (50Hz) 3500 kVA 4000 ekW

Engine Specifications

Engine Model 3512B TA, V-12, 4-Stroke Water-Cooled Diesel 3608 I-8,4-Stroke Water-Cooled Diesel C280-16, V-16,4-Stroke Water-Cooled Diesel C280-6, I-6,4-Stroke Water-Cooled Diesel C280-8, I-8,4-Stroke Water-Cooled Diesel 3516E, V-16, 4-Stroke Water-Cooled Diesel C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel
Bore 6.69 in 11 in 11 in 11 in 11 in 6.69 in 6.89 in
Stroke 7.48 in 11.8 in 11.8 in 11.8 in 11.8 in 8.46 in 8.66 in
Stroke - HD 8.46 in - - - - - -
Displacement 3161.03 in³ 9064 in³ 18032 in³ 111 in³ 9064 in³ 4765 in³ 6456.31 in³
Displacement - HD 3576 in³ - - - - - -
Compression Ratio 15.5:1 HD 13:01 13:01 13:01 13:01 14.0:1 15.3:1
Aspiration TA TA TA TA TA ATAAC Turbo Aftercooled
Fuel System Electronic Unit Injection Direct unit injection Direct unit injection Direct unit injection Direct unit injection Electronic Unit Injection Common Rail
Governor Type ADEM™ A3 Generator Set Monitoring System (GMS) Generator Set Monitoring System (GMS) Generator Set Monitoring System (GMS) Generator Set Monitoring System (GMS) Adem™ A5 ADEM� A4

Generator Set Dimensions

Length - Minimum 212.8 in - - - - 313.4 in 262.5 in
Length - Maximum 217.1 in 404 in 404 in 404 in 404 in 318.4 in 331.1 in
Width - Minimum 90 in - - - - 104 in 92 in
Width - Maximum 90 in 99.62 in 99.62 in 99.62 in 99.62 in 104 in 128.5 in
Height - Minimum 94.9 in - - - - 131.6 in 99.8 in
Height - Maximum 94.9 in 156.6 in 156.6 in 156.6 in 156.6 in 131.6 in 150.7 in
Dry Weight - Genset (minimum) 25620 lb - - - - 44930 lb 55100 lb
Dry Weight - Genset (maximum) 26530 lb 91050 lb 141840 lb 74970 lb 91050 lb 45651 lb 66200 lb
Add a Similar Product:
  • 3616 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3606 Generator Set (Medium Speed) Add
  • C175-16 Generator Set Add
  • C175-16 Tier 4 Final Add
  • 3516E Low Voltage Generator Set Add
  • 3516E Low Voltage Generator Set Add