Compare Equipment Go Back

G3520H Gas Generator
Cat Customizable Switchgear and Controls
XQP550 EU Stage V
EMCP 4.4 Master Control Panel
Cat Switchgear
Cat® BDP1000 Bi-Directional Power Inverter

Generator Set Specifications

Continuous Rating 2519 / 2500 ekW @ 1.0pf - - - - - -
Fuel Type Natural Gas, Hydrogen Blend (up to 25%) - - - - - -
Maximum Electrical Efficiency 45.30% - - - - - -
Frequency 50/60 Hz - - - - - -
RPM 1500 - - - - - -

Engine Specifications

Engine Model G3520H - - - - - -
Displacement 5956 in³ - - - - - -
Aspiration TA - - - - - -
Bore 6.7 in - - - - - -
Stroke 8.5 in - - - - - -
Compression Ratio 12.1 - - - - - -

Generator Set Dimensions

Length 302 in - - - - - -
Width 86 in - - - - - -
Height 97 in - - - - - -
Dry Weight - Genset 54675 lb - - - - - -

Technical Summary

Configuration - Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc - Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. - - -
Modes of Operation - All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow - Emergency standby, island, utility paralleling - - -
Application - LV and MV ( 208V - 38 kV) 50 / 60 Hz - LV and MV (208V - 38 kV) - - Energy Storage System
Technical Summary - - - - - Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. -
Module Type - - - - - - Integral part of Power Grid Stabilization and Energy Time Shift modules
Rated Power - - - - - - 1000 kVA (1000kW 1PF)

Generator Protective Devices

ANSI Protective Devices - Per customer specification - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 - - -

Utility Protective Devices

ANSI Protective Devices - Per customer specification - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) - - -

Environmental Parameters

Certifications - Per customer specification - IBC, CBC, UBC & OSHPD Certified - - -
Control Panel Enclosure - Per customer specification - NEMA 1 wall-mounted construction - - -
Operating Temperature - Per customer specification - 0°C to 50°C - - -
Storage Temperature - Per customer specification - -20°C to +60°C - - -
Low Voltage Standards - Per customer specification - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 - - -
Medium Voltage Standards - Per customer specification - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 - - -

Generator Set

Rating Prime - - 550 kVA - 340 ekW (425 kVA) - -
Frequency - - 50/60 Hz - 50/60 Hz - -
Voltage - - 220 - 480 V - 120 - 600 V - -
Fuel/Emissions Strategy - - EU Stage V - - - -
Rating Standby - - - - 375 ekW (469 kVA) - -

Engine

Engine - - Cat® C18 - C13 - -
Fuel - - Diesel - Diesel - -

Dimensions

Width - - 80.3 in - - - -
Height - - 90.5 in - - - -
Length - - 213.3 in - - - -
Weight - With Lube Oil and Coolant - - 14860 lb - - - -
Height - Without Trailer - - - - 60 in - -
Length - Without Trailer - - - - 208.7 in - -
Width - Without Trailer - - - - 104 in - -
Weight with Lube Oil and Coolant, Without Trailer - - - - 14700 lb - -
Standard Widths - - - - - 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. -
Standard Heights - - - - - Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping -
Standard Depths - - - - - 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers -

Fuel Consumption

100% Load 60 Hz - - 34.3 gal/hr - - - -
100% Load 50 Hz - - 33.4 gal/hr - - - -
75% Load 60 Hz - - 26.13 gal/hr - - - -
75% Load 50 Hz - - 24.9 gal/hr - - - -
100% Load 60Hz - - - - 25.1 gal/hr - -
75% Load 60Hz - - - - 19.2 gal/hr - -
50% Load 60Hz - - - - 13.6 gal/hr - -

Noise rating (with enclosure)

Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz) - - 79.19 - - - -
Sound Power @ 7 meters (23 feet) @ All Ratings - - - - 74 dB(A) - -

Enclosure Rating

Configuration - - - - - IP4X -

Operating Temperature

Operating Temperature - - - - - 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) -

Application

Application - - - - - LV 380…480 VAC, 50 Hz, 3-Phase. -

Modes of Operation

Modes of Operation - - - - - Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. -
Add a Similar Product:
  • Cat XLM Switchgear Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQ230 Rental Power Add
  • XQ125 Rental Power Add
  • XQ60 Add
  • XQ35 Add
  • CG260-16 Gas Generator Set Add