Generator Set Specifications
  • Maximum Rating - 400 kVA
  • Minimum Rating - 400 kVA
  • Emissions/Fuel Strategy - Non-Certified Emissions
  • Voltage - 380 to 415 Volts
  • Frequency - 50 Hz
  • Speed - 1500 rpm
  • Duty Cycle - Standby
Engine Specifications
  • Engine Model - C9.3B, I-6, 4-cycle diesel
  • Bore - 4.53in
  • Stroke - 5.87in
  • Displacement - 567.5in³
  • Compression Ratio - 16.5:1
  • Aspiration - Turbocharged Air-to-Air Aftercooled
  • Fuel System - Common Rail
  • Governor Type - ADEM™A6
Generator Set Dimensions
  • Length - Maximum - 104.8in
  • Width - Maximum - 44in
  • Height - Maximum - 69.5in
  • Dry Weight - Genset (maximum) - 5070.6lb
Standard Equipment:
  • Engine
    • C9.3B, Inline 6 cylinder, 4 stroke diesel
  • Air, Cooling & Exhaust
    • Standard air filter
  • Genset Control
    • GCCP 1.1
  • Governor
    • Adem A4
  • Alternator
    • A Frame standard alternator
  • Fuel Storage
    • Single wall 8 hour fuel tank
  • General
    • Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment:
  • Air, Cooling & Exhaust
    • 6" Elbow kit
    • Dual element air filter
    • 5-6" Exhaust adapter
    • Canopy silencer
    • 5" Elbow kit
    • 6" Elbow kit
    • 6" Muffler - 25 dBA attenuation
    • 5" Muffler - 10 dBA Attenuation
    • Single stage air filter
    • No muffler
  • Alternator Requirements
    • IP Standard @ 21 FUW A-Frame
    • Space heater
  • Auxiliary Supply Voltage
    • 240V
  • Certification
    • Australia, CIS, Gulf Certification
    • Certificate of Conformance 13
  • Circuit Breaker
    • 3 Pole Circuit breaker 800A
    • Circuit breaker padlock
    • 4 Pole Circuit breaker 630A
    • 4 Pole Circuit breaker 1250A
    • 3 Pole Circuit breaker 630A
    • 4 Pole Circuit breaker 800A
    • Overload via alarm switch on breaker
    • Neutral earth link
    • 3 Pole Circuit breaker 1250A
    • Auxiliary contacts
    • Shunt Trip
  • Enclosure
    • Cat GC enclosure
  • Fuel Storage
    • Low fuel level shutdown
    • Fuel level alarms
    • Low fuel level alarm
    • Single wall tank with containment 01
    • High fuel level alarm
    • Dual wall 8 hour fuel tank
  • Genset Control
    • PLG Cellular 4G E
    • Oil temperature displays
    • Coolant heater
    • Battery charger
    • Standby Pack (Smart Jacket water heater, Battery charger)
    • PLG Cellular 4G U
    • Voltage adjust potentiometer
    • Low coolant temperature alarm
    • Speed adjust potentiometer
    • PLG Ethernet
    • Battery