D250 GC (60 Hz) Generator Set
Product description
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications
- Maximum Rating - 250 ekW
- Minimum Rating - 250 ekW
- Emissions/Fuel Strategy - EPA Stationary Emergency
- Voltage - 208 to 600 Volts
- Frequency - 60 Hz
- Speed - 1800 rpm
- Duty Cycle - Standby
Engine Specifications
- Engine Model - Cat® C9 In-line 6, 4-cycle Diesel
- Bore - 4.4in
- Stroke - 5.9in
- Displacement - 538in³
- Compression Ratio - 16.3:1
- Aspiration - Turbocharged Air-to-Air Aftercooled
- Fuel System - HEUI
- Governor Type - Adem™A4
Generator Set Dimensions
- Length - Maximum - 155.5in
- Width - Minimum - 56.3in
- Width - Maximum - 56.7in
- Height - Minimum - 67.2in
- Height - Maximum - 86.7in
- Dry Weight - Genset (minimum) - 5324.2lb
- Dry Weight - Genset (maximum) - 6735.1lb
Standard Equipment:
-
- Air Inlet System
-
- Air cleaner - Non-Canister, Disposable
- Aftercooler core
- Turbocharger
-
- Control Panel
-
- GCCP 1.2
-
- Cooling System
-
- Jacket water pump, gear driven, centrifugal
- Radiator sight gauge
- Blower fan and fan drive with guards
- Thermostats and housing.
- Coolant drain valve.
- Radiator, Package mounted.
-
- Exhaust System
-
- Exhaust manifold; dry
-
- Fuel System
-
- Fuel priming pump
- Engine fuel transfer pump
- Primary fuel filter w/integral water separator and secondary filter, spin on
- Integral Tank Base, 24 Hrs, UL142
-
- Generator Set
-
- Factory tested to design specifications at full load conditions
- Complete system designed & built at ISO 9001:2000 certified facilities
- All protective devices and control functions simulated and checked
-
- Generators And Generator Attachments
-
- Easy access to AVR and terminals
- Insulation, Class H
- Brushless, self-excited 2/3 pitch (600V uses Internal Excitation)
- Voltage regulator (single phase sensing)
- Terminal Box, IP22 RHS Facing, Bottom Cable Entry
- 12 Leads
- Standard winding protection for non-harsh environments with relative humidity ? 95%
- IP23 protection
-
- Governing System
-
- Cat Electronic Governor (ADEM A4)
-
- Lube System
-
- Oil filler and dipstick.
- Lubricating Oil, CK-4 (10W-30)
- Shallow oil pan.
- Oil filter, spin on.
- Fumes disposal to front of radiator.
- Oil cooler
- Oil drain with valve.
-
- Mounting System
-
- Includes lifting provisions and termination points for coolant and lube oil drain lines
- Captive linear vibration isolators between base and engine-generator
-
- Protection
-
- Safety Shutoff - Overspeed
- Safety Shutoff - High water temperature
- Safety Shutoff - Low Oil Pressure
-
- Starting/charging System
-
- 24-volt electric starting motor.
- 24V, 45 amp charging alternator.
-
- General
-
- Vibration damper.
- Lifting Eyes
- Parts Book
Optional Equipment:
-
- Air Inlet System
-
- Air Cleaner (Non-Canister Disposable)
-
- Bases, Mounting & Fuel Tanks
-
- Integral Tank Base, 24 Hrs, UL142
- Audio & Visual Fuel Alarm (@90% Fuel Level)
- Wide Base - Skid
- Fuel Tank Fill Pipe & Lockable Cap
-
- Circuit Breaker
-
- 400A LS/I
- 600A LS/I
- 1200A LSI
- 600A LSI
- 1200A LS/I
- Auxiliary Contacts
- 400A LSI
- 800A LSI
- 800A LS/I
-
- Control System
-
- Twist Release, Red Button Emergency Stop
- Product Link Remote Monitoring hardware
- 16 -light NFPA 99/110 Annunciator
- Volt Free Contacts
- Ground Fault Relay
- 20A GFCI (Ground Fault Circuit Interrupter)
- Audible Alarm Gp
- 100A Load Center
-
- Enclosures
-
- E-Stop
- AC & DC Source Lights
- Sound Attenuated Level 2 Enclosure (White)
-
- Exhaust System
-
- 6" Muffler - 25 dBA Attenuation
- Flexible Exhaust Connection
- Manifold & Turbocharger Guards
-
- Generator
-
- Permanent Magnet Generator
- Space Heater
-
- Starting System
-
- Standard Battery Set: 1000 CCA, 90 amp/hr.
- Battery Charger (UL Certified)
- Jacket Water Heater
-
- General
-
- CSA Certification
- Extended Service Coverage
- Generator Test Report
- UL2200 Certification