3516C (50 Hz) with Upgradeable Package

Product description

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Generator Set Specifications
  • Standby Rating - 2750 kVA
  • Prime Power Rating - 2500 kVA
  • Emissions/Fuel Strategy - Low Fuel Consumption
  • Voltage - 380 to 11000 volts
  • Frequency - 50 Hz
  • Speed - 1500 rpm
  • Duty Cycle - Standby, Mission Critical, Prime
  • Maximum Rating - 2750 kVA
  • Minimum Rating - 2500 kVA
Engine Specifications
  • Engine Model - 3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel
  • Bore - 6.69in
  • Stroke - 8.46in
  • Displacement - 4765in
  • Compression Ratio - 14:01
  • Aspiration - TA
  • Fuel System - Electronic unit injection
  • Governor Type - Adem™3
Generator Set Dimensions
  • Length - Maximum - 228.3in
  • Width - Maximum - 75.9in
  • Height - Maximum - 80.7in
  • Dry Weight - Genset (maximum) - 32404lb
Standard Equipment:
  • Air Inlet System
    • Air cleaner
    • Single element canister type with service indicator
  • Control Panel
    • RPM
    • Engine cycle crank
    • Failure to start (overcrank)
    • Warning/shutdown with common LED indication of shutdowns for:
    • Speed adjust
    • True RMS AC metering, 3-phase, +/-2% accuracy
    • Accessory module data link
    • Overcurrent (50/51)
    • DC volts
    • Controls:
    • Generator phase sequence
    • Low oil pressure
    • 2 Programmable digital outputs
    • Reverse power (kW) (32)
    • Low coolant level
    • Operating hours
    • Frequency (Hz)
    • kVAr-hr (total)
    • kVA (per phase, average & percent)
    • Lamp test
    • Over/under frequency (81 o/u)
    • 6 programmable digital inputs
    • 2 Programmable relay outputs (Form C)
    • 24 Volt DC operation
    • Customer data link (Modbus RTU)
    • EMCP 4 Genset controller
    • Volts (L-L & L-N)
    • High coolant temperature
    • Alarm acknowledge
    • Oil pressure (psi, kPa or bar)
    • 4 Programmable relay outputs (Form A)
    • Overspeed
    • EMCP4.2B controller includes:
    • Engine cool-down timer
    • Panel lights
    • kW (per phase, average & percent)
    • Low coolant temperature
    • Over/under voltage (27/59)
    • Serial annunciator module data link
    • Generator mounted - rear facing
    • Communications:
    • kVAr (per phase, average & percent)
    • Digital indication for:
    • Text alarm/event descriptions
    • EMCP 4.2B
    • Coolant temperature
    • Emergency stop pushbutton
    • Programmable protective relaying functions:
    • kW-hr (total)
    • Reverse reactive power (kVAr) (32RV)
    • Amps (per phase & average)
    • Environmental sealed front face
    • Power factor (per phase & average)
  • Exhaust
    • Exhaust flange outlet
  • Fuel
    • Primary fuel filter with integral water separator
  • Generator
    • IP23 Protection
    • Matched to the performance and output characteristics of Cat engines
  • Power Termination
    • Busbar
  • Starting/charging
    • Heavy duty starting system
    • Charging alternator
  • Cooling System
    • Fan and belt guards
    • Coolant drain line with valve
    • JWAC
    • Caterpillar extended life coolant
    • Coolant level sensors
    • Radiator fan and fan drive
  • Cooling
    • Package mounted radiator
  • Exhaust System
    • Flanged faced outlet(s)
    • Dry exhaust manifold
  • Fuel System
    • Flexible fuel lines - shipped loose
    • Fuel priming pump
    • Fuel cooler; not included with packages without radiator
    • Secondary fuel filters
  • Generators And Attachments
    • NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby).
    • Busbar connections, top center mounted, top cable entry
    • Random wound
    • 6 Lead
    • Winding temperature detectors
    • IEC standard hole pattern
    • Internal excitation (IE)
    • 3 phase brushless, Salient pole
    • Generator set packages include Caterpillar's digital voltage regulator (CDVR). CDVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min/max exciter
  • Governing System
    • ADEM III
  • Literature
    • Parts book
    • Operation & Maintenance Manual
  • Lube System
    • Gear type lube oil pump
    • Integral lube Oil cooler
    • Fumes disposal
    • Lubricating oil
    • Oil filter, filler and dipstick
    • Oil drain lines and valve
  • Mounting System
    • Rails - Engine/generator/radiator mounting
    • Rubber anti-vibration mounts - shipped loose
  • Starting / Charging System
    • 24 Volt electric starting motor
    • Battery and battery rack w/cables
    • Battery disconnect switch
  • General
    • Right hand servicing
    • Flywheel and flywheel housing-SAE No. 00
    • Paint - Caterpillar yellow with high gloss black rails & radiator
    • SAE standard rotation
Optional Equipment:
  • Air Inlet System
    • Remote air inlet adapters
    • Dual element air cleaners
    • Air inlet protection
    • Heavy duty air cleaners
  • Circuit Breakers
    • Cable entry options
    • Control packaging for enclosures
    • Trip units
    • Load take off; IEC standard hole
    • Busbar power connections
    • Center posts busbars
    • EMAX breakers
  • Power Termination
    • Circuit breakers, IEC compliant
  • Control Panels
    • Annunciator modules
    • Generator temperature monitoring
    • Auxiliary box
    • Remote speed adjust
    • Busbar connections
    • Vandal proof panel door
    • Voltage raise/lower switch
    • EMCP 4.3, EMCP 4.4
    • Local and remote monitoring
    • Language options
    • Customer interface options
    • External box clips
    • EMAX breaker connections
    • Governors
  • Cooling System
    • Heat exchangers
    • Water level switch gauges
    • Radiator duct flanges
    • Optional Serpentine radiators
  • European Certifications
    • EU Declaration of Conformity
  • Exhaust System
    • Through wall installation kit
    • Muffler mounting kits
    • Mufflers
    • Flexible fittings
  • Fuel System
    • Fuel coolers
    • Primary fuel filter
  • Generators And Attachments
    • Generators
    • 3 Phase, Random wound, Internal excitation (IE)
    • Internal excitation (IE)
    • 3 Phase, 380 / 400 / 415 / 3300 / 6600 / 10000 / 10500 / 11000 volt
    • Number of leads: 6
    • Pitch: 0.6667
  • Instrumentation
    • Pyrometers and thermocouples
    • Thermocouples
  • Lube System
    • Oil level regulator
    • Electric prelube pumps
    • Manual prelube sump pumps
  • Mounting System
    • IBC vibration isolators
    • Spring type vibration isolators
  • Protection System
    • Explosion relief valves
  • Special Tests / Reports
    • IBC seismic Certification
    • CSA test and certification
    • PGS Test report @ 1.0 power factor
    • Neutral ground certificate
    • PGS Test report @ 0.8 power factor
  • Starting / Charging System
    • 10 and 20 Amp Battery chargers
    • Charging alternators - 50 Amp
    • Dual 24 volt electric starting motors
    • ETHER starting aids
    • 24 Volt battery set - Dry
    • Jacket water heaters
  • General
    • Engine barring group