Generator Set Specifications
  • Standby Rating - 1400/1250 kVA
  • Prime Power Rating - 1275/1150 kVA
  • Emissions/Fuel Strategy - Low Fuel Consumption
  • Voltage - 380 to 415 Volts
  • Frequency - 50 Hz
  • Speed - 1500 rpm
  • Duty Cycle - Standby, Mission Critical, Prime, Continuous
  • Maximum Rating - 1400 kVA
  • Minimum Rating - 1000 kVA
Engine Specifications
  • Engine Model - 3512 TA, V-12, 4-Stroke Water-Cooled Diesel
  • Bore - 6.69in
  • Stroke - 7.48in
  • Displacement - 3161.03in³
  • Compression Ratio - 13.5:1
  • Aspiration - TA
  • Fuel System - Direct Unit Injection
  • Governor Type - Woodward
Generator Set Dimensions
  • Length - Minimum - 202.7in
  • Length - Maximum - 206.6in
  • Width - Maximum - 77.8in
  • Height - Maximum - 93.2in
  • Dry Weight - Genset (minimum) - 22650lb
  • Dry Weight - Genset (maximum) - 23170lb
Standard Equipment:
  • Air Inlet System
    • Air cleaner; single element canister type with service indicator
  • Control Panel
    • EMCP4.2B controls includes: Emergency stop pushbutton
    • RPM
    • Engine cool-down timer
    • EMCP4.2B controller includes:
    • Accessory module data link
    • 4 programmable relay outputs (Form A)
    • Communications:
    • Volts (L-L & L-N)
    • Over/under frequency (81 o / u)
    • Text alarm/event descriptions
    • Auto/start/stop control
    • Speed adjust
    • kVA (per phase, average & percent)
    • Overcurrent (50 / 51)
    • Alarm acknowledge
    • Environmental sealed front face
    • 6 programmable digital inputs
    • Oil pressure (psi, kPa or bar)
    • Amps (per phase & average)
    • Generator phase sequence
    • 2 Programmable digital outputs
    • Low coolant temperature
    • Controls:
    • Serial annunciator module data link
    • Reverse power (kW) (32)
    • Lamp test
    • Coolant temperature
    • Engine cycle crank
    • kVAr-hr (total)
    • 2 Programmable relay outputs (Form C)
    • Generator mounted - rear facing
    • 24 Volt DC operation
    • kVAr (per phase, average & percent)
    • Warning/shutdown with common LED indication of shutdowns for:
    • kW (per phase, average & percent)
    • Reverse reactive power (kVAr) (32RV)
    • Programmable protective relaying functions:
    • Digital indication for:
    • High coolant temperature
    • Low oil pressure
    • Overspeed
    • Over/under voltage (27 / 59)
    • Customer data link (Modbus RTU)
    • DC volts
    • Operating hours
    • Low coolant level
    • kW-hr (total)
    • Frequency (Hz)
    • Emergency stop
    • Power factor (per phase & average)
    • Failure to start (overcrank)
    • True RMS AC metering, 3-phase, +/-2% accuracy
  • Cooling System
    • JWAC
    • Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)
    • Radiator fan and fan drive
    • Fan and belt guards
    • Coolant drain line with valve
    • Coolant level sensors (Not included with packages without radiator)
  • Exhaust System
    • Dry exhaust manifold
    • Flanged faced outlet(s)
  • Fuel System
    • Fuel cooler; not included with packages without radiator
    • Flexible fuel lines - shipped loose
    • Fuel priming pump
    • Secondary fuel filters
  • Generators And Attachments
    • Generator set packages include: Regulator (CDVR)
    • 6 Lead
    • Min / max exciter limiter
    • LV
    • Reactive droop capability
    • Random wound
    • Exciter diode monitor
    • KVAR/PF modes
    • NEMA Class H insulation
    • 50 Hz models: IEC standard hole pattern
    • Caterpillar's digital voltage regulator (CDVR) includes:
    • Note: 1800 Frames are form wound, permanent magnet excitation (PMG), with winding temp detectors
    • Busbar connections, top center mounted, top cable entry
    • Internal excitation (IE)
    • Winding temperature detectors
    • Class H temperature rise at 40C ambient (125C prime/150C standby)
    • 3 Phase brushless, Salient pole
    • 3 Phase voltage sensing
    • RFI suppression
  • Governing System
    • Woodward 2301A isochronous governor
  • Lube System
    • Oil drain lines and valve
    • Gear type lube oil pump
    • Fumes disposal
    • Oil filter, filler and dipstick
    • Lubricating oil
    • Integral lube Oil cooler
  • Mounting System
    • Rubber anti-vibration mounts - shipped loose
    • Rails - engine/generator/radiator mounting
  • Starting / Charging System
    • 24 Volt electric starting motor
    • Battery and battery rack w/cables
    • Battery disconnect switch
  • General
    • Paint - Caterpillar yellow with high gloss black rails & radiator
    • SAE standard rotation
    • RH service
    • Flywheel and Flywheel housing - SAE No. 00
Optional Equipment:
  • Air Inlet System
    • Remote air inlet adaptors
    • Air inlet protection
    • Dual element air cleaners
  • Circuit Breakers
    • EMAX Circuit breakers
    • Center posts busbars
    • EMAX breakers connections
    • Breaker harnesses
    • 2000, 2500, 3200 and 4000 Amp, 4 pole, IEC rated Circuit breakers
    • Controls packaging - Enclosures
    • Cable entry options
    • 2000, 2500, 3200 and 4000 Amp, 3 pole, IEC rated Circuit breakers
    • Optional busbar power connections
    • Busbar connections
  • Control Panel
    • Auxiliary boxes
    • Customer connection mounting locations
    • Ground (Automatically selected)
    • Vandle proof panel door
    • Customer Interface options
    • Mounting group - External box clips
    • Remote speed adjust
    • Generator temperature monitoring
    • Governors
    • Annunciator Modules
    • Local PC monitoring
  • Cooling System
    • Water level switch gauges
    • Heat exchangers
    • Optional radiator arrangements
  • European Certifications
    • EU Declaration of Conformity
    • Eurasian Conformity (EAC) mark
    • European Directive genset, DoI (Declaration of Incorporation)
    • European Union Certification
  • Exhaust System
    • Through-wall installation kit
    • Muffler mounting kits
    • Mufflers
    • Flexible fittings
  • Fuel System
    • Primary fuel filter
  • Generators And Attachments
    • 380 / 400 / 415 Volts @ 50 Hz, 3 phase, Form wound, Permanent magnet excitation (PMG), No. of leads = 6, pitch= 0.6667
    • 380/400/415volts @ 50 Hz, 3 phase, random wound, Permanent magnet excitation (PMG), No. of leads = 6, pitch= 0.6667
    • Generator conversion
    • 380/400/415volts @ 50 Hz, 3 phase, random wound, Internal excitation (IE), No. of leads = 6, pitch= 0.6667
    • Space heater
  • Instrumentation
    • Pyrometer and thermocouples
  • Lube System
    • Electric prelube pumps
    • Oil level reg-1 shallow pan
    • Manual prelube sump pumps
  • Mounting System
    • Spring type vibration isolators
    • IBC vibration isolators
  • Protection System
    • Explosion relief valves
  • Special Tests / Reports
    • Neutral grounding connection
    • IBC seismic Certifications
    • Neutral ground-LV
    • PGS Test report @ 1.0 power factor
    • PGS Test report @ 0.8 power factor
  • Starting / Charging Systems
    • Ether starting aid
    • 24 Volt dual electric starting motor
    • 20 Amp Battery charger
    • Oversize battery set
    • Jacket water heaters
    • 10 Amp Battery chargers
  • General
    • Engine barring group
Compare Products