3516E Low Voltage Generator Set
3512 Generator Set
C280-6 Generator Set (Medium Speed)

Generator Set Specifications

Standby Rating 2750 ekW 1400/1250 kVA -
Prime Power Rating 2500 ekW 1275/1150 kVA -
Emissions/Fuel Strategy Tier 2, Low NOx Low fuel, Low Emissions IMO Tier 2
Voltage 416 to 13,800 Volts 380 to 415 Volts -
Frequency 60 Hz 50 Hz 50 / 60 Hz
Speed 1800 rpm 1500 rpm 900 / 1000 rpm
Duty Cycle Standby, Mission Critical, Prime Standby, Mission Critical, Prime, Continuous Prime, Continuous
Maximum Rating 2750 ekW 1400 kVA 1820 ekW (60Hz), 2425 kVA (50Hz)
Minimum Rating 2500 ekW 1000 kVA 1650 ekW (60Hz), 2200 kVA (50Hz)

Engine Specifications

Engine Model 3516E, V-16, 4-Stroke, Water-Cooled Diesel 3512 TA, V-12, 4-Stroke Water-Cooled Diesel C280-6, I-6,4-Stroke Water-Cooled Diesel
Bore 6.69 in 6.69 in 11 in
Stroke 8.47 in 7.48 in 11.8 in
Displacement 4765 in³ 3161.03 in³ 111 in³
Compression Ratio 14.7:1 13.5:1 13:01
Aspiration ATAAC TA TA
Fuel System EUI Direct Unit Injection Direct unit injection
Governor Type Adem™ A5 Woodward Generator Set Monitoring System (GMS)

Generator Set Dimensions

Length - Maximum 303.3 in 207.5 in 404 in
Width - Maximum 104 in 79.3 in 99.62 in
Height - Maximum 131.6 in 92 in 156.6 in
Dry Weight - Genset (maximum) 40750 lb 23060 lb 74970 lb
Length - Minimum - 203.5 in -
Dry Weight - Genset (minimum) - 22540 lb -
Add a Similar Product:
  • 3616 Generator Set (Medium Speed) Add
  • C280-16 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C175-20 Add
  • 3606 Generator Set (Medium Speed) Add