Compare Equipment Go Back

Cat G3516H Combined Heat and Power (CHP) Solution
Cat Customizable Switchgear and Controls
Engine Paralleling and Integration Control (EPIC)

Generator Set Specifications

Continuous Rating 1982 ekW @ 1.0pf - -
Fuel Type Natural Gas - -
Maximum Electrical Efficiency 42.90% - -
Frequency 60 Hz - -
RPM 1500 - -

Engine Specifications

Engine Model G3516H - -
Displacement 4765 in³ - -
Aspiration TA - -
Bore 6.7 in - -
Stroke 8.5 in - -
Fuel System Electronic Fuel Control Valve - -
Governor Type ADEM™ A4 - -
Compression Ratio 11.1 - -

Generator Set Dimensions

Length 716 in - -
Width 155 in - -
Height 467 in - -
Dry Weight - Genset 40384 lb - -
Weight 166600 lb - -

Technical Summary

Configuration - Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation - All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application - LV and MV ( 208V - 38 kV) 50 / 60 Hz LV and MV (208V-27kV)

Generator Protective Devices

ANSI Protective Devices - Per customer specification 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Utility Protective Devices

ANSI Protective Devices - Per customer specification 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications - Per customer specification UL / cUL 508A
Control Panel Enclosure - Per customer specification NEMA 12
Operating Temperature - Per customer specification 0°C to 55°C
Storage Temperature - Per customer specification -20°C to 60°C
Low Voltage Standards - Per customer specification -
Medium Voltage Standards - Per customer specification -
Add a Similar Product:
  • Cat XLM Switchgear Add
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Temporary Connection Boxes Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • XQ425 Add