Compare Equipment Go Back

CG170B-16 Gas Generator Set
Temporary Connection Boxes
Cat EGP Switchgear
Cat Customizable Switchgear and Controls
XQ570 Tier 4 Final - 455 ekW (568 kVA)
XQP550 EU Stage V

Generator Set Specifications

Continuous Rating 1840 ekW @1.0pf - - - - -
Fuel Type Natural Gas, Biogas, Coal Gas, Hydrogen Blend (up to 25%) - - - - -
Maximum Electrical Efficiency 44.70% - - - - -
Maximum Standby Rating 1840 - - - - -
Frequency 50 Hz - - - - -
RPM 1500 rpm - - - - -

Engine Specifications

Engine Model CG170B-16 - - - - -
Aspiration TA - - - - -
Bore 6.7 in - - - - -
Stroke 7.7 in - - - - -

Generator Set Dimensions

Length 240 in - - - - -
Width 67 in - - - - -
Height 86 in - - - - -
Dry Weight - Genset 38360 lb - - - - -

Technical Summary

Application - EMERGENCY, LEGALLY REQUIRED EMERGENCY AND STANDBY LV and MV (208V - 38 kV) LV and MV ( 208V - 38 kV) 50 / 60 Hz - -
Module Type - LUG-TO-LUG, CAMLOCK AND ENCLOSED CIRCUIT BREAKER - - - -
Rated Power - 200 - 4000 AMPS - - - -
Configuration - - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc - -
Modes of Operation - - Multi-unit Island and multi-unit standby mode with optional redundant controls and components. All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow - -

Generator Protective Devices

ANSI Protective Devices - - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 Per customer specification - -

Environmental Parameters

Certifications - - IBC, CBC, UBC & OSHPD Certified Per customer specification - -
Control Panel Enclosure - - NEMA 1 or NEMA 3R Freestanding Construction Per customer specification - -
Operating Temperature - - 0°C to 50°C Per customer specification - -
Storage Temperature - - -20°C to +60°C Per customer specification - -
Low Voltage Standards - - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 Per customer specification - -
Medium Voltage Standards - - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 Per customer specification - -

Utility Protective Devices

ANSI Protective Devices - - - Per customer specification - -

Generator Set

Rating Prime - - - - 455 ekW (568 kVA) 550 kVA
Frequency - - - - 60 Hz 50/60 Hz
Voltage - - - - 120 - 600 V 220 - 480 V
Rating Standby - - - - 500 ekW (625 kVA) -
Fuel/Emissions Strategy - - - - - EU Stage V

Engine

Engine - - - - Cat C18 Cat® C18
Fuel - - - - Diesel Diesel

Dimensions

Height - Without Trailer - - - - 102 in -
Length - Without Trailer - - - - 240 in -
Width - Without Trailer - - - - 96 in -
Weight with Lube Oil and Coolant, Without Trailer - - - - 24125 lb -
Width - - - - - 80.3 in
Height - - - - - 90.5 in
Length - - - - - 213.3 in
Weight - With Lube Oil and Coolant - - - - - 14860 lb

Fuel Consumption

100% Load 60Hz - - - - 35.9 gal/hr -
75% Load 60Hz - - - - 28.3 gal/hr -
50% Load 60Hz - - - - 20.5 gal/hr -
100% Load 60 Hz - - - - - 34.3 gal/hr
100% Load 50 Hz - - - - - 33.4 gal/hr
75% Load 60 Hz - - - - - 26.13 gal/hr
75% Load 50 Hz - - - - - 24.9 gal/hr

Noise rating (with enclosure)

Sound Power @ 7 meters (23 feet) @ All Ratings - - - - 74 dB(A) -
Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz) - - - - - 79.19
Add a Similar Product:
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • XQ425 Add
  • XQ230 Rental Power Add
  • XQ125 Rental Power Add
  • XQ60 Add
  • XQ35 Add