Compare Equipment Go Back

CG170B-16 Gas Generator Set
Temporary Connection Boxes
Cat EGP Switchgear
Cat Customizable Switchgear and Controls

Generator Set Specifications

Continuous Rating 1840 ekW @1.0pf - - -
Fuel Type Natural Gas, Biogas, Coal Gas, Hydrogen Blend (up to 25%) - - -
Maximum Electrical Efficiency 44.70% - - -
Maximum Standby Rating 1840 - - -
Frequency 50 Hz - - -
RPM 1500 rpm - - -

Engine Specifications

Engine Model CG170B-16 - - -
Aspiration TA - - -
Bore 6.7 in - - -
Stroke 7.7 in - - -

Generator Set Dimensions

Length 240 in - - -
Width 67 in - - -
Height 86 in - - -
Dry Weight - Genset 38360 lb - - -

Technical Summary

Application - EMERGENCY, LEGALLY REQUIRED EMERGENCY AND STANDBY LV and MV (208V - 38 kV) LV and MV ( 208V - 38 kV) 50 / 60 Hz
Module Type - LUG-TO-LUG, CAMLOCK AND ENCLOSED CIRCUIT BREAKER - -
Rated Power - 200 - 4000 AMPS - -
Configuration - - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc
Modes of Operation - - Multi-unit Island and multi-unit standby mode with optional redundant controls and components. All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow

Generator Protective Devices

ANSI Protective Devices - - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 Per customer specification

Environmental Parameters

Certifications - - IBC, CBC, UBC & OSHPD Certified Per customer specification
Control Panel Enclosure - - NEMA 1 or NEMA 3R Freestanding Construction Per customer specification
Operating Temperature - - 0°C to 50°C Per customer specification
Storage Temperature - - -20°C to +60°C Per customer specification
Low Voltage Standards - - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 Per customer specification
Medium Voltage Standards - - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 Per customer specification

Utility Protective Devices

ANSI Protective Devices - - - Per customer specification
Add a Similar Product:
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add
  • XQ425 Add
  • XQ230 Rental Power Add
  • XQ125 Rental Power Add