Compare Equipment Go Back
CG170B-16 Gas Generator Set |
Temporary Connection Boxes |
Cat EGP Switchgear |
Cat® BDP1000 Bi-Directional Power Inverter |
|
Generator Set Specifications |
||||
---|---|---|---|---|
Continuous Rating | 1840 ekW @1.0pf | - | - | - |
Fuel Type | Natural Gas, Biogas, Coal Gas, Hydrogen Blend (up to 25%) | - | - | - |
Maximum Electrical Efficiency | 44.70% | - | - | - |
Maximum Standby Rating | 1840 | - | - | - |
Frequency | 50 Hz | - | - | - |
RPM | 1500 rpm | - | - | - |
Engine Specifications |
||||
Engine Model | CG170B-16 | - | - | - |
Aspiration | TA | - | - | - |
Bore | 6.7 in | - | - | - |
Stroke | 7.7 in | - | - | - |
Generator Set Dimensions |
||||
Length | 240 in | - | - | - |
Width | 67 in | - | - | - |
Height | 86 in | - | - | - |
Dry Weight - Genset | 38360 lb | - | - | - |
Technical Summary |
||||
Application | - | EMERGENCY, LEGALLY REQUIRED EMERGENCY AND STANDBY | LV and MV (208V - 38 kV) | Energy Storage System |
Module Type | - | LUG-TO-LUG, CAMLOCK AND ENCLOSED CIRCUIT BREAKER | - | Integral part of Power Grid Stabilization and Energy Time Shift modules |
Rated Power | - | 200 - 4000 AMPS | - | 1000 kVA (1000kW 1PF) |
Configuration | - | - | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications | - |
Modes of Operation | - | - | Multi-unit Island and multi-unit standby mode with optional redundant controls and components. | - |
Generator Protective Devices |
||||
ANSI Protective Devices | - | - | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | - |
Environmental Parameters |
||||
Certifications | - | - | IBC, CBC, UBC & OSHPD Certified | - |
Control Panel Enclosure | - | - | NEMA 1 or NEMA 3R Freestanding Construction | - |
Operating Temperature | - | - | 0°C to 50°C | - |
Storage Temperature | - | - | -20°C to +60°C | - |
Low Voltage Standards | - | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - |
Medium Voltage Standards | - | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - |