Compare Equipment Go Back

CG170B-16 Gas Generator Set
Temporary Connection Boxes
Cat EGP Switchgear
Cat® BDP1000 Bi-Directional Power Inverter

Generator Set Specifications

Continuous Rating 1840 ekW @1.0pf - - -
Fuel Type Natural Gas, Biogas, Coal Gas, Hydrogen Blend (up to 25%) - - -
Maximum Electrical Efficiency 44.70% - - -
Maximum Standby Rating 1840 - - -
Frequency 50 Hz - - -
RPM 1500 rpm - - -

Engine Specifications

Engine Model CG170B-16 - - -
Aspiration TA - - -
Bore 6.7 in - - -
Stroke 7.7 in - - -

Generator Set Dimensions

Length 240 in - - -
Width 67 in - - -
Height 86 in - - -
Dry Weight - Genset 38360 lb - - -

Technical Summary

Application - EMERGENCY, LEGALLY REQUIRED EMERGENCY AND STANDBY LV and MV (208V - 38 kV) Energy Storage System
Module Type - LUG-TO-LUG, CAMLOCK AND ENCLOSED CIRCUIT BREAKER - Integral part of Power Grid Stabilization and Energy Time Shift modules
Rated Power - 200 - 4000 AMPS - 1000 kVA (1000kW 1PF)
Configuration - - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications -
Modes of Operation - - Multi-unit Island and multi-unit standby mode with optional redundant controls and components. -

Generator Protective Devices

ANSI Protective Devices - - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 -

Environmental Parameters

Certifications - - IBC, CBC, UBC & OSHPD Certified -
Control Panel Enclosure - - NEMA 1 or NEMA 3R Freestanding Construction -
Operating Temperature - - 0°C to 50°C -
Storage Temperature - - -20°C to +60°C -
Low Voltage Standards - - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 -
Medium Voltage Standards - - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 -
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add
  • XQ425 Add
  • XQ230 Rental Power Add
  • XQ125 Rental Power Add