Compare Equipment Go Back
Cat Customizable Switchgear and Controls |
Cat XLM Switchgear |
XQP550 EU Stage V |
|
Technical Summary |
|||
---|---|---|---|
Configuration | Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications | - |
Modes of Operation | All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow | Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power | - |
Application | LV and MV ( 208V - 38 kV) 50 / 60 Hz | LV and MV ( 208V - 38 kV | - |
Generator Protective Devices |
|||
ANSI Protective Devices | Per customer specification | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | - |
Utility Protective Devices |
|||
ANSI Protective Devices | Per customer specification | 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 | - |
Environmental Parameters |
|||
Certifications | Per customer specification | IBS, CBC, UBC & OSHPD Certified | - |
Control Panel Enclosure | Per customer specification | NEMA 1 or NEMA 3R, Freestanding Construction | - |
Operating Temperature | Per customer specification | 0 degrees to 50 degrees C | - |
Storage Temperature | Per customer specification | -20 degrees C to +60 degrees C | - |
Low Voltage Standards | Per customer specification | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - |
Medium Voltage Standards | Per customer specification | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - |
Generator Set |
|||
Rating Prime | - | - | 550 kVA |
Frequency | - | - | 50/60 Hz |
Voltage | - | - | 220 - 480 V |
Fuel/Emissions Strategy | - | - | EU Stage V |
Engine |
|||
Engine | - | - | Cat® C18 |
Fuel | - | - | Diesel |
Dimensions |
|||
Width | - | - | 80.3 in |
Height | - | - | 90.5 in |
Length | - | - | 213.3 in |
Weight - With Lube Oil and Coolant | - | - | 14860 lb |
Fuel Consumption |
|||
100% Load 60 Hz | - | - | 129.7 gal/hr |
100% Load 50 Hz | - | - | 18.7 gal/hr |
75% Load 60 Hz | - | - | 0 gal/hr |
75% Load 50 Hz | - | - | 23.1 gal/hr |
Noise rating (with enclosure) |
|||
Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz) | - | - | 79.19 |
Add a Similar Product:
- Cat Switchgear Add
- Cat EGP Switchgear Add
- Engine Paralleling and Integration Control (EPIC) Add
- EMCP 4.4 Master Control Panel Add
- Energy Time Shift (ETS) Module Add
- Energy Capacity Expansion (ECE) module Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
- Temporary Connection Boxes Add
- XQ425 Add