Compare Equipment Go Back
Cat Customizable Switchgear and Controls |
EMCP 4.4 Master Control Panel |
Engine Paralleling and Integration Control (EPIC) |
|
Technical Summary |
|||
---|---|---|---|
Configuration | Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc | Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. | Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) |
Modes of Operation | All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow | Emergency standby, island, utility paralleling | Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) |
Application | LV and MV ( 208V - 38 kV) 50 / 60 Hz | LV and MV (208V - 38 kV) | LV and MV (208V-27kV) |
Generator Protective Devices |
|||
ANSI Protective Devices | Per customer specification | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) |
Utility Protective Devices |
|||
ANSI Protective Devices | Per customer specification | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) |
Environmental Parameters |
|||
Certifications | Per customer specification | IBC, CBC, UBC & OSHPD Certified | UL / cUL 508A |
Control Panel Enclosure | Per customer specification | NEMA 1 wall-mounted construction | NEMA 12 |
Operating Temperature | Per customer specification | 0°C to 50°C | 0°C to 55°C |
Storage Temperature | Per customer specification | -20°C to +60°C | -20°C to 60°C |
Low Voltage Standards | Per customer specification | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - |
Medium Voltage Standards | Per customer specification | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - |
Add a Similar Product:
- Cat Switchgear Add
- Cat XLM Switchgear Add
- Cat EGP Switchgear Add
- Energy Capacity Expansion (ECE) module Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- Energy Time Shift (ETS) Module Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
- Temporary Connection Boxes Add
- XQP550 EU Stage V Add
- XQ230 Rental Power Add