Cat Customizable Switchgear and Controls
XQ570 Tier 4 Final - 455 ekW (568 kVA)
Energy Time Shift (ETS) Module

Technical Summary

Configuration Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc - -
Modes of Operation All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow - -
Application LV and MV ( 208V - 38 kV) 50 / 60 Hz - Peak Shaving
Module Type - - Energy Time Shift
Nameplate Power - - 570 kW | 1000 kW
Nameplate Energy Capacity - - 1518 kWh

Generator Protective Devices

ANSI Protective Devices Per customer specification - -

Utility Protective Devices

ANSI Protective Devices Per customer specification - -

Environmental Parameters

Certifications Per customer specification - -
Control Panel Enclosure Per customer specification - -
Operating Temperature Per customer specification - -
Storage Temperature Per customer specification - -
Low Voltage Standards Per customer specification - -
Medium Voltage Standards Per customer specification - -

Generator Set

Rating Prime - 455 ekW (568 kVA) -
Frequency - 60 Hz -
Voltage - 120 - 600 V -
Rating Standby - 500 ekW (625 kVA) -

Engine

Engine - Cat C18 -
Fuel - Diesel -

Dimensions

Height - Without Trailer - 102 in -
Length - Without Trailer - 240 in -
Width - Without Trailer - 96 in -
Weight with Lube Oil and Coolant, Without Trailer - 24125 lb -

Fuel Consumption

100% Load 60Hz - 35.9 gal/hr -
75% Load 60Hz - 28.3 gal/hr -
50% Load 60Hz - 20.5 gal/hr -

Noise rating (with enclosure)

Sound Power @ 7 meters (23 feet) @ All Ratings - 74 dB(A) -
Add a Similar Product:
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • Cat EGP Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add
  • XQ230 Rental Power Add