Cat XLM Switchgear
Energy Capacity Expansion (ECE) module
EMCP 4.4 Master Control Panel

Technical Summary

Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications - Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source.
Modes of Operation Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power - Emergency standby, island, utility paralleling
Application LV and MV ( 208V - 38 kV Reserve Power Capacity LV and MV (208V - 38 kV)
Module Type - Energy Storage -
Nameplate Energy Capacity - 1518 kWh - 7590 kWh -

Generator Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51 - 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications IBS, CBC, UBC & OSHPD Certified - IBC, CBC, UBC & OSHPD Certified
Control Panel Enclosure NEMA 1 or NEMA 3R, Freestanding Construction - NEMA 1 wall-mounted construction
Operating Temperature 0 degrees to 50 degrees C - 0°C to 50°C
Storage Temperature -20 degrees C to +60 degrees C - -20°C to +60°C
Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Add a Similar Product:
  • Cat Switchgear Add
  • Cat Customizable Switchgear and Controls Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add
  • XQ230 Rental Power Add