Compare Equipment Go Back

Cat EGP Switchgear
3608 Generator Set (Medium Speed)

Technical Summary

Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications - -
Modes of Operation Multi-unit Island and multi-unit standby mode with optional redundant controls and components. - -
Application LV and MV (208V - 38 kV) - -

Generator Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51 - -

Environmental Parameters

Certifications IBC, CBC, UBC & OSHPD Certified - -
Control Panel Enclosure NEMA 1 or NEMA 3R Freestanding Construction - -
Operating Temperature 0°C to 50°C - -
Storage Temperature -20°C to +60°C - -
Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 - -
Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 - -

Generator Set Specifications

Maximum Rating - 3575 kVA -
Minimum Rating - 2363 kVA -
Emissions/Fuel Strategy - Low Fuel Consumption -
Frequency - 50 Hz -
Speed - 750 & 1000 rpm -
Duty Cycle - Standby, Prime, Continuous -

Engine Specifications

Engine Model - 3608 I-8,4-Stroke Water-Cooled Diesel -
Bore - 11 in -
Stroke - 11.8 in -
Displacement - 9064 in³ -
Compression Ratio - 13:01 -
Aspiration - TA -
Fuel System - Direct unit injection -
Governor Type - Generator Set Monitoring System (GMS) -

Generator Set Dimensions

Length - Maximum - 404 in -
Width - Maximum - 99.62 in -
Height - Maximum - 156.6 in -
Dry Weight - Genset (maximum) - 91050 lb -
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • EMCP 4.4 Master Control Panel Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add