Compare Equipment Go Back
Cat EGP Switchgear |
C175-20 |
|
|
Technical Summary |
|||
---|---|---|---|
Configuration | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications | - | - |
Modes of Operation | Multi-unit Island and multi-unit standby mode with optional redundant controls and components. | - | - |
Application | LV and MV (208V - 38 kV) | - | - |
Generator Protective Devices |
|||
ANSI Protective Devices | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | - | - |
Environmental Parameters |
|||
Certifications | IBC, CBC, UBC & OSHPD Certified | - | - |
Control Panel Enclosure | NEMA 1 or NEMA 3R Freestanding Construction | - | - |
Operating Temperature | 0°C to 50°C | - | - |
Storage Temperature | -20°C to +60°C | - | - |
Low Voltage Standards | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - | - |
Medium Voltage Standards | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - | - |
Generator Set Specifications |
|||
Standby Rating | - | 4000 (no fan)/3900/3620(no fan)/3500 ekW | - |
Prime Power Rating | - | 3600 (no fan)/3500/3300 (no fan)/3180 ekW | - |
Emissions/Fuel Strategy | - | Low Fuel, Tier 2 | - |
Voltage | - | 480 to 13800 Volts | - |
Frequency | - | 60 Hz | - |
Speed | - | 1800 rpm | - |
Duty Cycle | - | Standby, Mission Critical, Prime, Continuous | - |
Maximum Rating | - | 4000 ekW | - |
Minimum Rating | - | 3150 ekW | - |
Engine Specifications |
|||
Engine Model | - | C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel | - |
Bore | - | 6.89 in | - |
Stroke | - | 8.66 in | - |
Displacement | - | 6456.31 in³ | - |
Compression Ratio | - | 15.3:1 | - |
Aspiration | - | Turbo Aftercooled | - |
Fuel System | - | Common Rail | - |
Governor Type | - | ADEM� A4 | - |
Generator Set Dimensions |
|||
Length - Minimum | - | 261.5 in | - |
Length - Maximum | - | 330.6 in | - |
Width - Minimum | - | 85.4 in | - |
Width - Maximum | - | 127.7 in | - |
Height - Minimum | - | 87.6 in | - |
Height - Maximum | - | 150.7 in | - |
Dry Weight - Genset (minimum) | - | 55100 lb | - |
Dry Weight - Genset (maximum) | - | 66200 lb | - |
Add a Similar Product:
- Cat Switchgear Add
- Cat XLM Switchgear Add
- Cat Customizable Switchgear and Controls Add
- Engine Paralleling and Integration Control (EPIC) Add
- EMCP 4.4 Master Control Panel Add
- Energy Capacity Expansion (ECE) module Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- Temporary Connection Boxes Add
- Energy Time Shift (ETS) Module Add
- XQP550 EU Stage V Add