Cat EGP Switchgear
Cat XLM Switchgear

Technical Summary

Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications -
Modes of Operation Multi-unit Island and multi-unit standby mode with optional redundant controls and components. Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power -
Application LV and MV (208V - 38 kV) LV and MV ( 208V - 38 kV -

Generator Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51 15/25, 27/59, 81 O/U, 32, 40, 50, 51 -

Environmental Parameters

Certifications IBC, CBC, UBC & OSHPD Certified IBS, CBC, UBC & OSHPD Certified -
Control Panel Enclosure NEMA 1 or NEMA 3R Freestanding Construction NEMA 1 or NEMA 3R, Freestanding Construction -
Operating Temperature 0°C to 50°C 0 degrees to 50 degrees C -
Storage Temperature -20°C to +60°C -20 degrees C to +60 degrees C -
Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 -
Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 -

Utility Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 -
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat Switchgear Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add