Compare Equipment Go Back
Cat EGP Switchgear |
Cat Customizable Switchgear and Controls |
|
|
Technical Summary |
|||
---|---|---|---|
Configuration | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications | Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc | - |
Modes of Operation | Multi-unit Island and multi-unit standby mode with optional redundant controls and components. | All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow | - |
Application | LV and MV (208V - 38 kV) | LV and MV ( 208V - 38 kV) 50 / 60 Hz | - |
Generator Protective Devices |
|||
ANSI Protective Devices | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | Per customer specification | - |
Environmental Parameters |
|||
Certifications | IBC, CBC, UBC & OSHPD Certified | Per customer specification | - |
Control Panel Enclosure | NEMA 1 or NEMA 3R Freestanding Construction | Per customer specification | - |
Operating Temperature | 0°C to 50°C | Per customer specification | - |
Storage Temperature | -20°C to +60°C | Per customer specification | - |
Low Voltage Standards | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | Per customer specification | - |
Medium Voltage Standards | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | Per customer specification | - |
Utility Protective Devices |
|||
ANSI Protective Devices | - | Per customer specification | - |
Add a Similar Product:
- Cat Switchgear Add
- Cat XLM Switchgear Add
- Engine Paralleling and Integration Control (EPIC) Add
- EMCP 4.4 Master Control Panel Add
- Energy Time Shift (ETS) Module Add
- Energy Capacity Expansion (ECE) module Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
- Temporary Connection Boxes Add
- XQ425 Add