Cat EGP Switchgear
Cat XLM Switchgear
Engine Paralleling and Integration Control (EPIC)

Technical Summary

Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation Multi-unit Island and multi-unit standby mode with optional redundant controls and components. Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application LV and MV (208V - 38 kV) LV and MV ( 208V - 38 kV LV and MV (208V-27kV)

Generator Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51 15/25, 27/59, 81 O/U, 32, 40, 50, 51 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Environmental Parameters

Certifications IBC, CBC, UBC & OSHPD Certified IBS, CBC, UBC & OSHPD Certified UL / cUL 508A
Control Panel Enclosure NEMA 1 or NEMA 3R Freestanding Construction NEMA 1 or NEMA 3R, Freestanding Construction NEMA 12
Operating Temperature 0°C to 50°C 0 degrees to 50 degrees C 0°C to 55°C
Storage Temperature -20°C to +60°C -20 degrees C to +60 degrees C -20°C to 60°C
Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 -
Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 -

Utility Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)
Add a Similar Product:
  • Cat Switchgear Add
  • Cat Customizable Switchgear and Controls Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • Temporary Connection Boxes Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add
  • XQ230 Rental Power Add