Compare Equipment Go Back

EMCP 4.4 Master Control Panel
MX350 Controller

Technical Summary

Configuration Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. - -
Modes of Operation Emergency standby, island, utility paralleling - -
Application LV and MV (208V - 38 kV) - -
Rating Range - Switch Dependent -
Transfer Type - Application Dependent -
Switch Type - Application Dependent -

Generator Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51 - -

Utility Protective Devices

ANSI Protective Devices 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) - -

Environmental Parameters

Certifications IBC, CBC, UBC & OSHPD Certified - -
Control Panel Enclosure NEMA 1 wall-mounted construction - -
Operating Temperature 0°C to 50°C - -
Storage Temperature -20°C to +60°C - -
Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 - -
Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 - -

Controller Specifications

Voltage Unbalance on Dropout for Source 1 and Source 2 - 5 to 20% of nominal -
Delay NeutralTransition Time Delays (DT,DW) - 0-10 minutes -
Control Power - 120 VAC -
Undervoltage Dropout for Source 1 and Source 2 - 75-99% of nominal -
Undervoltage Restore for Source 1 and Source 2 - 85-100% of nominal -
Overfrequency Dropout for Source 1 and Source 2 - 50.1 - 63 Hz -
Source Sensing - 120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A) -
Delay for Engine Cool Down (U) - 0-60 minutes -
Underfrequency Restore for Source 1 and Source 2 - 45 - 59.5 Hz -
Load Control Relay Contacts (2) - 0-259 minutes -
Overvoltage Dropout for Source 1 and Source 2 - 105 - 110% of nominal -
Voltage Unbalance for Restore for Source 1 and Source 2 - 4 to 19% of nominal -
Storage Temperature - (-40˚C - 90˚C ) -
Underfrequency Dropout for Source 1 and Source 2 - 45 - 59.9 Hz -
Overfrequency Restore for Source 1 and Source 2 - 50 - 62.9 Hz -
Delay Transfer to Nonpreferred Source (W) - 0-5 minutes -
Operating Temperature Ambient - (-20˚C to 50˚C) -
Communications Interface - Optional - Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T) -
Overvoltage Restore for Source 1 and Source 2 - 103 - 108% of nominal -
Load Control Relay Contacts (1) - rated for 10A @ 24VDC or 120VAC -
Add a Similar Product:
  • MX250 Microprocessor Controller Add
  • CTSM and CTGM Series Manual Transfer Switches Add
  • CTX Series Automatic Transfer Switch Add
  • MX150 Microprocessor Controller Add
  • CTGSE & CTGDSE Series Service Rated Entrance Rated Automatic Transfer Switch Add
  • CTS Series Automatic Transfer Switch Add
  • CTE Series Automatic Transfer Switch Add
  • CTG Series Automatic Transfer Switch Add
  • Cat XLM Switchgear Add
  • Cat Customizable Switchgear and Controls Add