Compare Equipment Go Back

EMCP 4.4 Master Control Panel
Cat Customizable Switchgear and Controls

Technical Summary

Configuration Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc -
Modes of Operation Emergency standby, island, utility paralleling All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow -
Application LV and MV (208V - 38 kV) LV and MV ( 208V - 38 kV) 50 / 60 Hz -

Generator Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51 Per customer specification -

Utility Protective Devices

ANSI Protective Devices 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) Per customer specification -

Environmental Parameters

Certifications IBC, CBC, UBC & OSHPD Certified Per customer specification -
Control Panel Enclosure NEMA 1 wall-mounted construction Per customer specification -
Operating Temperature 0°C to 50°C Per customer specification -
Storage Temperature -20°C to +60°C Per customer specification -
Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 Per customer specification -
Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 Per customer specification -
Add a Similar Product:
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • Cat XLM Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQ425 Add