Compare Equipment Go Back

EMCP 4.4 Master Control Panel
Cat XLM Switchgear
Cat Customizable Switchgear and Controls

Technical Summary

Configuration Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc
Modes of Operation Emergency standby, island, utility paralleling Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow
Application LV and MV (208V - 38 kV) LV and MV ( 208V - 38 kV LV and MV ( 208V - 38 kV) 50 / 60 Hz

Generator Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51 15/25, 27/59, 81 O/U, 32, 40, 50, 51 Per customer specification

Utility Protective Devices

ANSI Protective Devices 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 Per customer specification

Environmental Parameters

Certifications IBC, CBC, UBC & OSHPD Certified IBS, CBC, UBC & OSHPD Certified Per customer specification
Control Panel Enclosure NEMA 1 wall-mounted construction NEMA 1 or NEMA 3R, Freestanding Construction Per customer specification
Operating Temperature 0°C to 50°C 0 degrees to 50 degrees C Per customer specification
Storage Temperature -20°C to +60°C -20 degrees C to +60 degrees C Per customer specification
Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 Per customer specification
Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 Per customer specification
Add a Similar Product:
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQ425 Add
  • XQP550 EU Stage V Add