Compare Equipment Go Back
EMCP 4.4 Master Control Panel |
Cat EGP Switchgear |
Cat® BDP1000 Bi-Directional Power Inverter |
|
Technical Summary |
|||
---|---|---|---|
Configuration | Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications | - |
Modes of Operation | Emergency standby, island, utility paralleling | Multi-unit Island and multi-unit standby mode with optional redundant controls and components. | - |
Application | LV and MV (208V - 38 kV) | LV and MV (208V - 38 kV) | Energy Storage System |
Module Type | - | - | Integral part of Power Grid Stabilization and Energy Time Shift modules |
Rated Power | - | - | 1000 kVA (1000kW 1PF) |
Generator Protective Devices |
|||
ANSI Protective Devices | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | - |
Utility Protective Devices |
|||
ANSI Protective Devices | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) | - | - |
Environmental Parameters |
|||
Certifications | IBC, CBC, UBC & OSHPD Certified | IBC, CBC, UBC & OSHPD Certified | - |
Control Panel Enclosure | NEMA 1 wall-mounted construction | NEMA 1 or NEMA 3R Freestanding Construction | - |
Operating Temperature | 0°C to 50°C | 0°C to 50°C | - |
Storage Temperature | -20°C to +60°C | -20°C to +60°C | - |
Low Voltage Standards | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - |
Medium Voltage Standards | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - |
Add a Similar Product:
- Cat Switchgear Add
- Cat XLM Switchgear Add
- Cat Customizable Switchgear and Controls Add
- Engine Paralleling and Integration Control (EPIC) Add
- Energy Capacity Expansion (ECE) module Add
- Temporary Connection Boxes Add
- Energy Time Shift (ETS) Module Add
- XQ425 Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
- XQP550 EU Stage V Add