Compare Equipment Go Back
Engine Paralleling and Integration Control (EPIC) |
MX250 Microprocessor Controller |
|
|
Technical Summary |
|||
---|---|---|---|
Configuration | Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) | - | - |
Modes of Operation | Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) | - | - |
Application | LV and MV (208V-27kV) | - | - |
Rating Range | - | Switch Dependent | - |
Transfer Type | - | Application Dependent | - |
Switch Type | - | Application Dependent | - |
Generator Protective Devices |
|||
ANSI Protective Devices | 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) | - | - |
Utility Protective Devices |
|||
ANSI Protective Devices | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) | - | - |
Environmental Parameters |
|||
Certifications | UL / cUL 508A | - | - |
Control Panel Enclosure | NEMA 12 | - | - |
Operating Temperature | 0°C to 55°C | - | - |
Storage Temperature | -20°C to 60°C | - | - |
Controller Specifications |
|||
Undervoltage Dropout for Source 1 and Source 2 | - | 75-98% of nominal | - |
Undervoltage Restore for Source 1 and Source 2 | - | 85-100% of nominal | - |
Underfrequency Dropout for Source 1 and Source 2 | - | 90-100% of nominal | - |
Delay for Engine Cool Down (U) | - | 0-60 minutes | - |
Delay Transfer to Nonpreferred Source (W) | - | 0-5 minutes | - |
Delay NeutralTransition Time Delays (DT,DW) | - | 0-10 minutes | - |
Storage Temperature | - | (-30˚C - 75˚C ), -22˚F - 167˚F | - |
Operating Temperature Ambient | - | 40 - 400 amp molded shell (-20˚C to 65˚C) , -4˚F to 149˚F 40 - 4000 amp all others (-20˚C to 60˚C), -4˚F to 149˚F |
- |
Add a Similar Product:
- MX350 Controller Add
- MX150 Microprocessor Controller Add
- CTSM and CTGM Series Manual Transfer Switches Add
- CTX Series Automatic Transfer Switch Add
- CTGSE & CTGDSE Series Service Rated Entrance Rated Automatic Transfer Switch Add
- CTS Series Automatic Transfer Switch Add
- Cat Switchgear Add
- CTE Series Automatic Transfer Switch Add
- CTG Series Automatic Transfer Switch Add
- Cat Customizable Switchgear and Controls Add