Compare Equipment Go Back

Engine Paralleling and Integration Control (EPIC)
Cat Customizable Switchgear and Controls
Cat XLM Switchgear

Technical Summary

Configuration Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application LV and MV (208V-27kV) LV and MV ( 208V - 38 kV) 50 / 60 Hz LV and MV ( 208V - 38 kV

Generator Protective Devices

ANSI Protective Devices 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) Per customer specification 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) Per customer specification 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

Environmental Parameters

Certifications UL / cUL 508A Per customer specification IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure NEMA 12 Per customer specification NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature 0°C to 55°C Per customer specification 0 degrees to 50 degrees C
Storage Temperature -20°C to 60°C Per customer specification -20 degrees C to +60 degrees C
Low Voltage Standards - Per customer specification NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - Per customer specification NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Add a Similar Product:
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Temporary Connection Boxes Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • XQP550 EU Stage V Add
  • XQ425 Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add