Compare Equipment Go Back

Engine Paralleling and Integration Control (EPIC)
Cat Customizable Switchgear and Controls

Technical Summary

Configuration Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc -
Modes of Operation Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow -
Application LV and MV (208V-27kV) LV and MV ( 208V - 38 kV) 50 / 60 Hz -

Generator Protective Devices

ANSI Protective Devices 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) Per customer specification -

Utility Protective Devices

ANSI Protective Devices 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) Per customer specification -

Environmental Parameters

Certifications UL / cUL 508A Per customer specification -
Control Panel Enclosure NEMA 12 Per customer specification -
Operating Temperature 0°C to 55°C Per customer specification -
Storage Temperature -20°C to 60°C Per customer specification -
Low Voltage Standards - Per customer specification -
Medium Voltage Standards - Per customer specification -

Generator Set

Rating Prime - - 340 ekW (425 kVA)
Frequency - - 50/60 Hz
Voltage - - 120 - 600 V
Rating Standby - - 375 ekW (469 kVA)

Engine

Engine - - C13
Fuel - - Diesel

Dimensions

Height - Without Trailer - - 60 in
Length - Without Trailer - - 208.7 in
Width - Without Trailer - - 104 in
Weight with Lube Oil and Coolant, Without Trailer - - 14700 lb

Fuel Consumption

100% Load 60Hz - - 25.1 gal/hr
75% Load 60Hz - - 19.2 gal/hr
50% Load 60Hz - - 13.6 gal/hr

Noise rating (with enclosure)

Sound Power @ 7 meters (23 feet) @ All Ratings - - 74 dB(A)
Add a Similar Product:
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • Cat XLM Switchgear Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Temporary Connection Boxes Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add